10 configuring the profibus slave, Configuring the profibus slave ( 40), 6commissioning of profibus – Lenze PROFIBUS Controller-based Automation User Manual
Page 40

6
Commissioning of PROFIBUS
6.2
Detailed commissioning steps
40
Lenze · Controller-based Automation · PROFIBUS® Communication Manual · DMS 4.3 EN · 04/2014 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2.10
Configuring the PROFIBUS slave
Set the DP Parameters for the PROFIBUS slave.
• The PROFIBUS slave
station address is automatically assigned after adding the slave to the
control configuration tree. The PROFIBUS master receives the station address ’0’, the first slave
the address ’1’, the second slave the address ’2’, and so on.
Do only change this setting if the station addresses shall deviate from the standard setting. If
required, you must manually adapt the station addresses of the other PROFIBUS stations, too.
Each station address in a PROFIBUS network must be unique (it must only appear once).
• You do not have to set a baud rate, as the slave automatically recognises the baud rate.
• By means of the
Groups... button, you can assign the slave to one (or several) device
group(s).
• We recommend not to change the other standard settings.