5.2
Bus cable specification
PROFIBUS cables with an integrated bus terminating resistor can be obtained from various cable
manufacturers.
Bus cable length
The length of the bus cable depends on the baud rate used:
Note!
Only use cables that comply with the specifications of the PROFIBUS user organisation.
Area
Values
Cable resistance
135 ... 165 /km, (f = 3 ... 20 MHz)
Capacitance per unit length
30 nF/km
Loop resistance
< 110 /km
Core diameter
> 0.64 mm
Core cross-section
> 0.34 mm
2
Cores
Twisted in pairs, insulated and shielded
Baud rate
Length
9.6 ... 93.75 kbps
1200 m
187.5 kbps
1000 m
500 kbps
400 m
1500 kbps
200 m
3000 ... 12000 kbps
100 m
Note!
The baud rate depending on the data volume, cycle time and number of stations should
only be selected as high as required for the application.