beautypg.com

2 bus cable specification, Bus cable specification, 5technical data – Lenze PROFIBUS Controller-based Automation User Manual

Page 24

background image

5

Technical data

5.2

Bus cable specification

24

Lenze · Controller-based Automation · PROFIBUS® Communication Manual · DMS 4.3 EN · 04/2014 · TD17

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.2

Bus cable specification

PROFIBUS cables with an integrated bus terminating resistor can be obtained from various cable

manufacturers.

Bus cable length
The length of the bus cable depends on the baud rate used:

Note!

Only use cables that comply with the specifications of the PROFIBUS user organisation.

Area

Values

Cable resistance

135 ... 165 /km, (f = 3 ... 20 MHz)

Capacitance per unit length

30 nF/km

Loop resistance

< 110 /km

Core diameter

> 0.64 mm

Core cross-section

> 0.34 mm

2

Cores

Twisted in pairs, insulated and shielded

Baud rate

Length

9.6 ... 93.75 kbps

1200 m

187.5 kbps

1000 m

500 kbps

400 m

1500 kbps

200 m

3000 ... 12000 kbps

100 m

Note!

The baud rate depending on the data volume, cycle time and number of stations should

only be selected as high as required for the application.