6

Commissioning of PROFIBUS

6.2

Detailed commissioning steps

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

3. Go to the "Add device" dialog box, select the respective slave field device from the

selection list and use the

Add device button to add it below the PROFIBUS master.

You can only select those devices the PROFIBUS device description file of which has been

imported in the »PLC Designer«.

Importing missing devices / device description files

( 32)

4. Repeat the

Add Device command until all slaves connected to the fieldbus are included

in the control configuration.

• In the control configuration, a maximum of 125 PROFIBUS slaves (devices) can be

appended below a PROFIBUS master.

• For each slave, a maximum of 244 input bytes and 244 output bytes, respectively, can be

transferred. Their data type is irrelevant in this context.