8

2.3 Replacing a defective Slave (without teach-in of actuator)

All safety slaves without necessity for teach-in of an actuator can be replaced without using a
PC with ASiMon according to this method.

1. Disconnect the defective slave from AS-Interface Bus

2. Press the service button on the monitor

– The monitor stores which slave address is missing

3. Connect new slave with address 0 AND bring it into a safe state

– The master addresses this slave automatically

4. Press the service button on the monitor

– The monitor has a check on the safety function of the new slave