3.5 Replacing a defective slave (with teach-in of actuator)


If an AS-i safety slave is defective, it can be replaced even without a PC or reconfiguration of
the AS-i Safety Monitor by pressing the ESC/Service key on the AS-i Safety Monitor.

All safety slaves with necessity for teach-in of an actuator like CES and CET can be replaced
without using a PC with ASiMon according to this method.

Proceed as follows:

1. Disconnect defective slave from AS-i bus.

2. Connect new slave with address 0

The monitor addresses this slave automatically

3. Teach-in of actuator according to operation manual

4. Dissconnect new slave from AS-Interface Bus

5. Press the ESC/Service button on the AS-i Safety Monitor approx. 3 seconds.





6. Connect new slave AND bring into safe state

7. Press the ESC/Service button on the AS-i Safety Monitor approx. 3 seconds.

The code table for the new slave is taught and checked for correctness. If this is OK,

the AS-i Safety Monitor changes to protecting mode.