Led diagnostics at sfm monitors – EUCHNER AS User Manual

Page 13

background image

Safety Monitors - AS-i Quick Reference - 08/2014

13

LEDs

Reason

Action

Failure on AS-i
Monitor has no data
transfer to master

Check AS-i bus,
setup of master

SFM

Power

Fault

Ready

ON

OFF

Monitor waits for
new slave or is
empty

Push service button
or load monitor new

SFM

Power

Fault

Ready

ON

OFF

According LED on

According LED
blinking

LED off

Don’t care

Monitor waits for
new slave or is
empty

Push service button
or load monitor new

SFM

Power

Fault

Ready

ON

OFF

Resetable fault at
safe slave.

Fault is NOT in
monitor!

Quick help: power
off and on of
monitor.

Help:
Connect PG with
ASIMON and check
which address is in
state „yellow
blinking“.

SFM

Power

Fault

Ready

ON

OFF

Resetable fault at
safe slave.

Fault is NOT in
monitor!

Quick help: power
off and on of
monitor.

Help:
Connect PG with
ASIMON and check
which address is in
state „yellow
blinking“.

SFM

Power

Fault

Ready

ON

OFF

Non resetable fault
at safe slave.

Fault is NOT in
monitor!

Connect PG with
ASIMON and check
which address is in
state „red blinking“.
teach this slave new
or replace it.

SFM

Power

Fault

Ready

ON

OFF

Monitor defective

Replace monitor

SFM

Power

Fault

Ready

ON

OFF

LEDs

Ursache

Maßnahme

Non resetable fault
at safe slave.

Fault is NOT in
monitor!

Connect PG with
ASIMON and check
which address is in
state „red blinking“.
teach this slave new
or replace it.

SFM

Power

Fault

Ready

ON

OFF

LED diagnostics at SFM monitors

Important:
With many of these failures there is no fault in the monitor. With
some failures a quick help is given by switching off and on the
monitor. For long term help the failure has to be detected.