beautypg.com

Software asimon, Diagnostics with software asimon, 4 software asimon – EUCHNER AS User Manual

Page 31: 1 diagnostics with software asimon

background image

Safety Monitors - AS-i Quick Reference - 08/2014

31

4 Software ASiMon

4.1 Diagnostics with Software ASiMon



Display

Colour

Meaning

green,
continuous

Device is in the ON state (switched on)

green,
flashing

Device is in the ON state (switched on), but already in the process
of being switched to the OFF state, e.g. switch-off delay

yellow,
continuous

Device is ready, but still waiting for another condition, e.g. local
acknowledgement, diagnosis stop or start button

yellow,
flashing

A (start) test must be performed, bring slave into OFF state and
then into ON state

red,
continuous

Device is in the OFF state (switched off)

rot,
flashing

The error lock is active, release by means of one of the following
actions:
Reset of error condition with the Service button
Power OFF/ON
AS-Interface bus OFF/ON

grey,
off

No communication with the AS-interface slave


circuit diagram display















With Strg + T and Strg + S can be switched between circuit diagram display and tree
structure display

Tree structure display