Software asimon, Diagnostics with software asimon, 4 software asimon – EUCHNER AS User Manual
Page 31: 1 diagnostics with software asimon
Safety Monitors - AS-i Quick Reference - 08/2014
31
4 Software ASiMon
4.1 Diagnostics with Software ASiMon
Display
Colour
Meaning
green,
continuous
Device is in the ON state (switched on)
green,
flashing
Device is in the ON state (switched on), but already in the process
of being switched to the OFF state, e.g. switch-off delay
yellow,
continuous
Device is ready, but still waiting for another condition, e.g. local
acknowledgement, diagnosis stop or start button
yellow,
flashing
A (start) test must be performed, bring slave into OFF state and
then into ON state
red,
continuous
Device is in the OFF state (switched off)
rot,
flashing
The error lock is active, release by means of one of the following
actions:
Reset of error condition with the Service button
Power OFF/ON
AS-Interface bus OFF/ON
grey,
off
No communication with the AS-interface slave
circuit diagram display
With Strg + T and Strg + S can be switched between circuit diagram display and tree
structure display
Tree structure display