beautypg.com

EUCHNER AS User Manual

Page 21

background image

Safety Monitors - AS-i Quick Reference - 08/2014

21

3.6 Reset Safety Error (caused by exchange of a safety slave)


When exchanging safety slaves, especially within combined machines a safety error can
occur, when the method according to 4.4 “Replacing a defective slave” was not used. When
one GMOx did not learn the new safety code, this fault occurs. This device can learn the new
code also without repeating the full procedure.

1. Press OK-button

2. Select AS-I SAFETY and press OK-button

3. Select TEACH SAFETY and press OK-button

4. Select SINGLE SLAVE and press OK-button

5. Enter PIN, when used and select OK and press OK-button


6. Select AS-I circuit fort he slave to teach and press OK-button

CODES LERNEN
PIN EINGEBE
0000
OK

TEACH CODES
COMPLETE
SINGLE SLAVE
COUPLING SLAVE
SNGL SLAVE_CODE

TEACH SAFETY
SAFE OUTPUT CH
SAFE COUPLING
START / STOP
CLEAR SAFE CFG
PIN
SAFE CHIPCARD
PROTECT
SAFE SUBST VAL


1 OFF 2 OFF

3 OFF 4 OFF

PROFIBUS
QUICK SETUP
AS-I SAFETY
DIAGNOSIS
SLAVE ADR TOOL
TEST
SETUP
DISP CONTRAST