States of asi safety parts, 3 states of asi safety parts – EUCHNER AS User Manual
Page 5
Safety Monitors - AS-i Quick Reference - 08/2014
5
1.3 States of ASi safety parts
LED State
Description
ASI
green
Fault or State
red
on
off
Normal operation
AS-Interface power connected
on
on
No data transfer between master and slave.
Reason:
-
Master in STOP-Mode
-
Slave not in LPS
-
Slave with wrong IO/ID
-
Reset at slave active
blinking *
on
No data transfer between master and slave.
Reason: Slave-Address = 0
blinking or on
blinking *
Device failure in slave.
Please contact EUCHNER.
*
Blinking LEDs are not supported from all safety switches
LPS
List Projected Slaves
IO/ID Slave profile to identify a slaves (Defined by manufacturer)
CET:
State LED ASI
Description
Green
Normal operation
Red
No data transfer between master and slave.
Reason:
-
Master in STOP-Mode
-
Slave not in LPS
-
Slave with wrong IO/ID
Red / Yellow
Alternately blinking
No data transfer between master and slave.
Reason: Slave-Address = 0
Red/green
Alternately blinking
Red blinking
Auxiliary power not connected or device failure in slave.
Please contact EUCHNER.