Safety Monitors - AS-i Quick Reference - 08/2014

5

1.3 States of ASi safety parts



LED State

Description

ASI

green

Fault or State

red

on

off

Normal operation

AS-Interface power connected

on

on

No data transfer between master and slave.

Reason:

-

Master in STOP-Mode

-

Slave not in LPS

-

Slave with wrong IO/ID

-

Reset at slave active

blinking *

on

No data transfer between master and slave.

Reason: Slave-Address = 0

blinking or on

blinking *

Device failure in slave.

Please contact EUCHNER.


*

Blinking LEDs are not supported from all safety switches

LPS

List Projected Slaves

IO/ID Slave profile to identify a slaves (Defined by manufacturer)


CET:

State LED ASI

Description

Green

Normal operation

Red

No data transfer between master and slave.

Reason:

-

Master in STOP-Mode

-

Slave not in LPS

-

Slave with wrong IO/ID

Red / Yellow

Alternately blinking

No data transfer between master and slave.

Reason: Slave-Address = 0

Red/green

Alternately blinking

Red blinking

Auxiliary power not connected or device failure in slave.