Det-Tronics R8471NH34001,2,3 Single Channel Gas Controller, NH3 User Manual
Page 22

95-8529
1.1
20
CURRENT OUTPUT CALIBRATION
The 4 to 20 milliampere output is calibrated at 
the factory to provide a degree of accuracy that 
is satisfactory for most applications. However, 
the highest level of accuracy can be obtained by 
performing the following procedure.
1. A dc current meter capable of measuring 4 to 20
milliamperes must be connected to the current loop 
output. This can be accomplished by connecting a 
dc ammeter in series with the load or by connecting 
a digital dc voltmeter across a known load 
resistance and calculating the current flow using the 
formula:
I = voltage/load resistance.
2. Press
and
hold
the Set button, then
immediately
press the Reset button. (The Reset button must 
be pressed within one second of pressing the 
Set button.) Release both buttons. The Low LED 
flashes slowly while the system generates a 4 ma 
output.
3. Press the Reset (increase) or Set (decrease) button
to obtain a 4.0 ma reading on the meter. (Holding 
the button will cause the output to change rapidly.)
4. When no adjustments have been made for 5
seconds, the controller automatically switches to a 
20 ma output. This is indicated by a flashing High 
LED. Press the appropriate button to obtain a 20.0 
ma reading.
5. When no adjustments have been made for 5
seconds, the controller generates the current output 
level for the calibrate mode. This is indicated by 
a flashing CAL LED. Press the appropriate button 
to obtain the desired current output level for the 
calibrate mode. (The default level is 4.0 ma.)
6. When no changes have been made for 5 seconds,
the system automatically returns to the Normal 
operating mode and saves the data in non-volatile 
memory.
7. Remove the meter from the system output and
reconnect the outputs for normal operating 
conditions.
