Det-Tronics R8471NH34001,2,3 Single Channel Gas Controller, NH3 User Manual
Page 18

95-8529
1.1
16
Section III
System Startup
STARTUP PROCEDURE
1. Output loads that are controlled by the system
should be secured (remove power from all output 
devices) to prevent actuation.
2. Check all external wiring. Be sure that the sensor
has been wired properly.
3. Before installing the controller in the mounting rack,
inspect it to verify that it has not been physically 
damaged in shipment. Check the jumper plugs 
and rocker switches on the controller for proper 
programming, then slide the controller fully into the 
mounting rack.
4. Apply power to the system.
NOTE
When power is applied to the system, the 
controller enters a time delay mode before 
beginning normal operation. During this time 
the outputs are inhibited, the FAULT LED is 
illuminated, and the current output indicates a 
fault condition. This delay allows time for the 
sensor output to stabilize before normal operation 
is begun. The controller will remain in the time 
delay mode up to five minutes or until the sensor 
output is within normal range (no fault or alarm 
conditions exist). At the end of the time delay, 
the controller automatically enters the Normal 
operating mode.
5. Put the controller in the Setpoint Display mode
to determine the present alarm setpoints and 
calibration gas time. If changes are required, 
perform the Setpoint Adjustment procedure.
6. Perform the calibration procedure.
7. Check the 4 to 20 ma current loop for proper
calibration and adjust as required.
8. Remove mechanical blocking devices (if used) and
restore power to the output loads.
SETPOINT ADJUSTMENT
To
check
the present levels, use the “Setpoint Display
Mode” described below. To
change
the values, use
the “Setpoint Adjustment Procedure.”
NOTE
In the Setpoint Display or Setpoint Adjust mode, 
a flashing alarm LED identifies the particular 
setpoint currently being indicated on the digital 
display. A flashing CAL LED indicates that the 
programmed calibration gas time is currently 
being shown on the digital display.
SETPOINT DISPLAY MODE
NOTE
In the Setpoint Display and Setpoint Adjust 
modes, the digital display indicates the 
calibration gas time in increments of 16 seconds. 
To determine the total calibration gas time 
indicated by the display, the reading indicated 
on the display must be multiplied by 16 seconds. 
To determine the number that should be used 
for programming the controller for the correct 
calibration time, determine the desired calibration 
time in minutes (five minutes is recommended), 
then multiply by 60 seconds, then divide by 16. 
For example, to program the controller for a 
calibration time of five minutes:
5 minutes X 60 seconds = 300 seconds
300 seconds ÷ 16 seconds = 18.75 units
Programming the controller for a reading of “19” 
produces a calibration time of five minutes and 
four seconds.
1. To enter the Setpoint Display mode, press and hold
the Reset button until the Low LED begins to blink 
(approximately one second). Release the Reset 
button. The low alarm setpoint will be shown for two 
seconds on the digital display.
NOTE
The Reset button should be released as soon 
as the controller has entered the Setpoint 
Display mode (after one second). If the button 
is still depressed at the end of the Setpoint 
Display mode (9 seconds), the controller will 
automatically enter the Calibrate mode. If the 
operator is not prepared to perform a calibration, 
a calibration fault will occur. Recycle power to 
the controller to exit the calibrate mode without 
affecting the calibration settings.
