Det-Tronics R8471NH34001,2,3 Single Channel Gas Controller, NH3 User Manual
Page 13

11
95-8529
1.1
The controller is designed for installation in a non-
hazardous area.
Figure 10 shows the terminal configuration for the 
controller.
Terminals 1 and 2 –
4 to 20 ma dc output.
Non-Isolated Current Output
-
If the 4 to 20 ma current loop 
is to be non-isolated, wire 
the current loop as shown in 
Figure 11. Note that terminal 2 
is not used with a non-isolated 
current loop. Program the 
controller for a non-isolated 
current loop as described in 
the “Controller Programming” 
section of this manual.
Isolated Current Output -
If
an isolated current loop is 
desired, wire the current loop 
as shown in Figure 12 and 
program the controller for 
an isolated current loop as 
described in the “Controller 
Programming” section of this 
manual. Note that this wiring 
scheme requires an external 
power source for the isolated 
current output. 
1
A1476
FIRE CONTROLLERS ARE APPROX. TWO INCHES
WIDE AND REQUIRE TWO GUIDE RAILS FOR
INSERTION. PLACE THE RETAINING CLIP BETWEEN
RAILS TO FORM SETS, LEAVE A GAP BETWEEN SETS.
SET
SET
GAP
1
2
3
2
THE Q4004 CONTROLLER CAGE HAS BEEN MODIFIED
TO ACCOMMODATE EITHER FIRE OR GAS CONTROLLERS
OR ANY COMBINATION OF THE TWO.
BY FOLLOWING THE INSTRUCTIONS BELOW, THE CAGE
CAN BE SET UP TO ANY CONFIGURATION.
2
TO INSERT A BLANK PANEL, PLACE A CLIP IN
THE TOP BRACKET IN LINE WITH THE CLIP IN THE
BOTTOM BRACKET.
3
GAS CONTROLLERS ARE APPROX. ONE INCH WIDE
AND REQUIRE ONE RAIL FOR INSERTION. PLACE CLIPS
IN LINE WITH GUIDE RAILS, CAGES WILL ACCEPT AS
MANY GAS CONTROLLERS AS RAILS PROVIDED.
Figure 9—Clip Positioning for Mounting Racks
CURRENT OUTPUT
CHASSIS GROUND
POWER
SENSOR
EXTERNAL RESET
HIGH ALARM
HIGH ALARM / OC
AUX. ALARM
AUX. ALARM / OC
LOW ALARM
LOW ALARM / OC
FAULT
FAULT / OC
1
3
4
5
6
7
8
9
10
11
12
13
14
15
16
–
+
+
–
+
–
18 TO 32
VDC
POWER
SIGNAL
2
OC = OPEN COLLECTOR OUTPUT
(BASE MODEL ONLY)
B1390
Figure 10—Controller Terminal Configuration
