DCR-1003 and DCR-1004

Rev. A3, 10/08

38

Automation Products Group, Inc.

APG...Providing tailored solutions for measurement applications

Tel: 1/888/525-7300 • Fax: 1/435/753-7490 • www.apgsensors.com • [email protected]

Y = measured distance

X = DCR Reading

A = Multiplier

B = Offset

The multiplier (A) can be determined by taking ultrasonic readings at two

known distances and dividing the difference of the known distances (D) by the
difference of the ultrasonic (U) readings (A) = (D

2

-D

1

)/ (U

2

-U

1

) where;

D

2

= far known distance

U

2

= Ultrasonic reading at D

2

D

1

= close known distance

U

1

= Ultrasonic reading at D

1

Enter this multiplier in Modes 47 and 48. The multiplier can then be entered

in the above equation to calculate the offset B = D

2

- (A)U

2

. The offset should

be entered using Modes 45 and 46.

Utilities

Reset
When the DCR is powered up, ‘NO’ is loaded in mode 49. This saves the

user-selected modes into the DCR. If the mode adjustments get scrambled or if
the factory preset values are wanted, press the NUM UP key. If ‘YES’ is
entered, the DCR will perform a reset, loading all the modes with the default
parameters.

MODE DESCRIPTION

PARAMETERS

EXPLANATION

49

Reset

Range = no - yes

Reset the mode parameters to

Default = no

their factory preset values
(default)
Set by NUM UP or NUM DN

Software Version
Mode 50 displays the software version for the DCR. The value corresponds

to the operating version and the approximate date of manufacture.

MODE DESCRIPTION

PARAMETERS

EXPLANATION

50

Software Version

Displays the software version