DIFFERENTIAL
The DCR-1003, 1004 can determine the difference between two levels. This is

accomplished by installing two DSTs at the same height, one over each level to
be monitored. The DSTs are then programmed as different sensor numbers, # 1
and # 2. The DCR-Controller will take the two level readings and display the
difference.

MODE DESCRIPTION

PARAMETERS

EXPLANATION

36

Change Sensor

Units = sensor #

Selects which number to assign

Number

Range = 1 - 2

to the sensor connected to the

Default = none

DCR.

ONLY ONE SENSOR SHOULD BE

Set by NUM UP or NUM DN

CONNECTED WHEN USING THIS MODE

37

Display Control

Units = sensor #

Selects which sensor distance

Range = 0 - 2

will be displayed. Default is the

0 - display differential

difference between DST #1 and

1 - display sensor #1

DST #2.

2 - display sensor #2
Default = 0

Example 7: Differential Reading
A mechanical rake is to be engaged for cleaning a screen when the upstream

level is 2 feet higher than the downstream level. To program the DCR-1003, 1004
for this application, the following modes must be changed from their preset
values.

MODE

VALUE

DESCRIPTION

Operation

3

3

Select Differential Monitoring for application

5

2.00

Do not set closer than the minimum distance
recommended for the DST sensor type being used

Relay

12

2.00

Begin trip point # 1 when the difference between levels is
greater than 2 ft.

13

3.00

Set the end point beyond the begin point

14

3

Set the trip type to ‘far’, meaning the relay will energize for
display readings greater than 2 ft.