Electrical system – JLG 4013PS Service Manual User Manual

Page 230

background image

Electrical System

9-90

3508PS, 3509PS, 3512PS, 3513PS, 4008PS, 4009PS, 4012PS, 4013PS, 4017PS, 40.8, 40.9

LSI DETECTED BUT
NOT CONFIGURED

8515

1

Inhibit all hydraulic functions.

Set CAN message bit to permit LSI
System display control of its alarm.

The UGM has detected the CAN

bus LSI system is present on the

machine; however it has not been

configured properly in the

MACHINE SETUP - LOAD

MOMENT menu selection.

Use analyzer

and correct

parameter

that is

improperly

configured.

LSI LOAD CELL A –
OUT OF RANGE

8516

1

If active, the control system will
respond as if the Load Moment

Cutout % parameter has been
reached and react accordingly

depending on the MARKET

configuration.

Set CAN message bit to permit LSI
System display control of its alarm.

The LSI System has detected that

Load Cell A is out of range and is

providing a CAN bus message

notification to the UGM.

Power cycle.

LSI LOAD CELL B –
OUT OF RANGE

8517

1

If active, the control system will
respond as if the Load Moment

Cutout % parameter has been
reached and react accordingly

depending on the MARKET

configuration.

Set CAN message bit to permit LSI
System display control of its alarm.

The LSI System has detected that

Load Cell B is out of range and is

providing a CAN bus message

notification to the UGM.

Power cycle.

LSI CUTOUT
OUTPUT – SHORT
TO BATTERY OR
OPEN CIRCUIT

8518

1

If active, the control system will
respond as if the Load Moment

Cutout % parameter has been
reached and react accordingly

depending on the MARKET

configuration.

Set CAN message bit to permit LSI
System display control of its alarm.

The LSI System has detected that

its 100% Cutout digital output has

an short to battery or open circuit

condition and is providing a CAN

bus message notification to the

UGM.

Power cycle.

LSI OUT OF
CALIBRATION

8519

1

If active, the control system will
respond as if the Load Moment

Cutout % parameter has been
reached and react accordingly

depending on the MARKET

configuration.

Set CAN message bit to permit LSI
System display control of its alarm.

The UGM LSI-CAN system check

has been performed and the actual

load cell raw counts are not within

+/- 10 counts of the logged

calibrated counts.

The LSI-CAN

system check

is performed

and is

completed

with a pass

condition.

STEERING

86XXX

LOW STEERING
PRESSURE

8638

1, 8

N/A

J1-35 Steering Pressure is HIGH for

a period of 3 seconds or more and

an ENGINE RUNNING state must

be detected for at least 5 seconds.

Until steer

pressure is

re-estab-

lished (i.e.

J1-35 is LOW

for a period of

3 seconds).

HARDWARE

99XXX

LSS WATCHDOG
RESET

991

1

Power

cycle.

(Replace

board)

Message

Fault

Code

Indicators

Other Actions Taken

Trigger for Fault

Latch Until