Electrical system – JLG 4013PS Service Manual User Manual
Page 204
Electrical System
9-64
3508PS, 3509PS, 3512PS, 3513PS, 4008PS, 4009PS, 4012PS, 4013PS, 4017PS, 40.8, 40.9
MAIN LIFT DOWN
VALVE –
OPEN CIRCUIT
33184
1
Deactivate output J2-22 Main Lift
Down Valve.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cycled.
MAIN LIFT DOWN
VALVE –
SHORT TO
GROUND
33185
1
Deactivate output J2-22 Main Lift
Down Valve.
Decouple/disable current feedback
input J3-2 Lift Return (Disables Lift
Up and Down).
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cycled.
MAIN TELESCOPE
OUT VALVE – OPEN
CIRCUIT
33186
1
Deactivate output J2-35 Main
Telescope Out Valve.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason why.
Power cycled.
MAIN TELESCOPE
VALVES – SHORT
TO BATTERY
33187
1
Deactivate output J2-35 Main
Telescope Out Valve.
Deactivate output J2-34 Main
Telescope In Valve.
Decouple/disable current feedback
input J3-4 Telescope Return
(Disables Telescope Out and In).
The UGM detects a short to battery
at this output.
Power cycled.
MAIN TELESCOPE
OUT VALVE –
SHORT TO
GROUND
33188
1
Deactivate output J2-35 Main
Telescope Out Valve.
Decouple/disable current feedback
input J3-4 Telescope Return
(Disables Telescope Out and In).
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cycled.
MAIN TELESCOPE
IN VALVE – OPEN
CIRCUIT
33189
1
Deactivate output J2-34 Main
Telescope In Valve.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cycled.
MAIN TELESCOPE
IN VALVE – SHORT
TO GROUND
33190
1
Deactivate output J2-34 Main
Telescope In Valve.
Decouple/disable current feedback
input J3-4 Telescope Return
(Disables Telescope Out and In).
The UGM detects a short to ground
at this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cycled.
FORK TILT UP
VALVE –
OPEN CIRCUIT
33191
1
Deactivate output J2-8 Fork Tilt Up
Valve.
The UGM detects an open circuit at
this output or the UGM detects a
CURRENT FEEDBACK LOST
condition and sets an internal flag to
determine if this fault condition is
the reason for the fault.
Power cycled.
Message
Fault
Code
Indicators
Other Actions Taken
Trigger for Fault
Latch Until