Electrical system – JLG 4013PS Service Manual User Manual
Page 210

Electrical System
9-70
3508PS, 3509PS, 3512PS, 3513PS, 4008PS, 4009PS, 4012PS, 4013PS, 4017PS, 40.8, 40.9
LEFT STABILIZER
UP VALVE – SHORT
TO GROUND
33227
1
Deactivate output J2-3 Right
Stabilizer Up Valve.
Deactivate output J2-15 Right
Stabilizer Down Valve.
Deactivate output J2-10 Left
Stabilizer Up Valve.
Deactivate output J2-21 Left
Stabilizer Down Valve.
The stabilizers are configured in the
MACHINE SETUP menu and the
UGM detects a short to ground at
this output.
Power cycled.
RIGHT STABILIZER
DOWN VALVE –
OPEN CIRCUIT
33228
1
Deactivate output J2-15 Right
Stabilizer Down Valve.
Deactivate output J2-21 Left
Stabilizer Down Valve
.
The stabilizers are configured in the
MACHINE SETUP menu and the
UGM detects an open circuit at this
output.
Power cycled.
RIGHT STABILIZER
DOWN VALVE –
SHORT TO
BATTERY
33229
1
Deactivate output J2-3 Right
Stabilizer Up Valve.
Deactivate output J2-15 Right
Stabilizer Down Valve.
Deactivate output J2-10 Left
Stabilizer Up Valve.
Deactivate output J2-21 Left
Stabilizer Down Valve.
Deactivate and inhibit output J1-3
(Frame Leveling and Stabilizers will
be cutout).
The stabilizers are configured in the
MACHINE SETUP menu and the
UGM detects a short to battery at
this output.
Power cycled.
RIGHT STABILIZER
DOWN VALVE –
SHORT TO
GROUND
33230
1
Deactivate output J2-15 Right
Stabilizer Down Valve.
Deactivate output J2-21 Left
Stabilizer Down Valve.
The stabilizers are configured in the
MACHINE SETUP menu and the
UGM detects a short to ground at
this output.
Power cycled.
RIGHT STABILIZER
UP VALVE – OPEN
CIRCUIT
33231
1
Deactivate output J2-3 Right
Stabilizer Up Valve.
Deactivate output J2-15 Right
Stabilizer Down Valve.
Deactivate output J2-10 Left
Stabilizer Up Valve.
Deactivate output J2-21 Left
Stabilizer Down Valve.
The stabilizers are configured in the
MACHINE SETUP menu and the
UGM detects an open circuit at this
output.
Power cycled.
RIGHT STABILIZER
UP VALVE – SHORT
TO BATTERY
33232
1
Deactivate output J2-3 Right
Stabilizer Up Valve.
Deactivate output J2-15 Right
Stabilizer Down Valve.
Deactivate output J2-10 Left
Stabilizer Up Valve.
Deactivate output J2-21 Left
Stabilizer Down Valve.
Deactivate and inhibit output
(Frame Leveling and Stabilizers will
be cutout).
The stabilizers are configured in the
MACHINE SETUP menu and the
UGM detects a short to battery at
this output.
Power cycled.
Message
Fault
Code
Indicators
Other Actions Taken
Trigger for Fault
Latch Until