Determining the status of a power supply – Brocade Communications Systems Brocade Backbone DCX 8510-4 User Manual
Page 73
![background image](/manuals/54677/73/background.png)
Brocade DCX 8510-4 Backbone Hardware Reference Manual
53
53-1002177-05
Determining the status of a power supply
4
for a map of the ports and a table of external ports to internal ports
as shown in the slotShow command
Determining the status of a power supply
Complete the following steps to determine the status of a power supply.
1. Check the LED indicator on the power supply (see the following figure). The LED patterns may
temporarily change during POST and other diagnostic tests; for information about how to
interpret the LED patterns, refer to
. The Brocade DCX 8510-4 has two power supplies.
Be sure to check each module.
2. Check the power supply status by entering psShow.
The power supply status displays OK, Absent, or Faulty. If a power supply displays absent or
faulty, contact the Brocade DCX 8510-4 supplier to order replacement parts. Both physically
absent or faulty could also be the result of the power supply not being properly seated or being
turned off.
shows a power supply.
QSFP
connector
status LED
No light (LED is off)
No QSFP module, all four
QSFP ports are disabled
No action needed if the QSFP is not
installed or
verify that the QSFP is fully inserted.
Steady amber
QSFP module is in, all four
ports have no signal/no
sync.
Ensure that the cable is properly
connected. If the LED remains
amber, consult the Brocade DCX
8510-4 supplier.
Blinking amber
Port is disabled or faulted,
FC link activity, segmented,
loopback mode, also
during transition between
cable plug in and all four
ports online.
Check for console messages or wait
for all four ports to come online.
Steady green
QSFP module is in and all
ports are online.
No action needed.
TABLE 5
CR blade LED descriptions (Continued)
LED purpose
Color
Status
Recommended action
1