Table 2 – ARI COOLING RATING TABLES
UNIT
NOM.
CAPACITY
(TONS)
NET COOLING
CAPACITY
(KBTU / HR)
TOTAL
POWER (KW)
SEER
EER
IPLV
IEER
04
3
34.6
3.1
13.0
11.0
N/A
N/A
05
4
45.0
4.0
13.0
11.0
N/A
N/A
06
5
59.0
5.5
13.0
10.8
N/A
N/A
07
6
70.0
6.4
N/A
11.0
N/A
11.4
LEGEND
ARI
--- Air---Conditioning & Refrigeration Institute
ASHRAE --- American Society of Heating, Refrigerating
and Air Conditioning, Inc.
EER
--- Energy Efficiency Ratio
IEER
--- Integrated Energy Efficiency Ratio
SEER
--- Seasonal Energy Efficiency Ratio
IPLV
--- Integrated Part Load Value
This product has been designed and manufactured to
meet Energy Star® criteria for energy efficiency.
However, proper refrigerant charge and proper air flow
are critical to achieve rated capacity and efficiency.
Installation of this product should follow all
manufacturer’s refrigerant charging and air flow
instructions.
Failure to confirm proper charge and
air flow may reduce energy efficiency and shorten
equipment life.
NOTES
1. Rated and certified under ARI Standard 210/240---06 or
360/360---04, as appropriate.
2. Ratings are based on:
Cooling Standard: 80_F (27_C) db, 67_F (19_C) wb
indoor air temp and 95_F (35_C) db outdoor air temp.
IPLV Standard: 80_F (27_C) db, 67_F (19_C) wb indoor
air temp and 80_F (27_C) db outdoor air temp.
IEER Standard: Procedure described in ARI Standard
340/360.
3. All 558J units comply with ASHRAE 90.1 2001, 2004
Energy Standard for minimum SEER and EER
requirements.
4. Where appropriate, 558J units comply with US Energy
Policy Act (2005). Refer to state and local codes or visit
the following website: http://bcap---energy. org to
determine if compliance with this standard pertains to
your state, territory, or municipality.
558J