FAN PERFORMANCE (cont.)
Table 19 – 558J*05
3 PHASE
4 TON HORIZONTAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
643
0.23
762
0.35
860
0.46
944
0.58
1020
0.71
1300
674
0.28
791
0.40
887
0.52
970
0.65
1045
0.78
1400
706
0.33
820
0.45
914
0.59
997
0.72
1071
0.86
1500
738
0.38
849
0.52
942
0.66
1024
0.80
1097
0.95
1600
771
0.44
879
0.59
971
0.74
1051
0.89
1124
1.04
1700
804
0.51
910
0.66
1000
0.82
1079
0.98
1151
1.14
1800
837
0.59
941
0.75
1029
0.91
1107
1.08
1178
1.25
1900
871
0.67
972
0.84
1059
1.02
1136
1.19
1206
1.37
2000
906
0.76
1004
0.94
1089
1.12
1165
1.31
1234
1.49
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
1200
1089
0.84
1153
0.98
1212
1.12
1269
1.26
1322
1.41
1300
1114
0.92
1177
1.06
1236
1.21
1292
1.36
1346
1.52
1400
1139
1.01
1202
1.15
1261
1.31
1316
1.47
1369
1.63
1500
1164
1.10
1227
1.25
1285
1.41
1341
1.58
1394
1.75
1600
1190
1.20
1252
1.36
1311
1.53
1366
1.70
1418
1.87
1700
1217
1.31
1278
1.48
1336
1.65
1391
1.83
1443
2.01
1800
1244
1.42
1305
1.60
1362
1.78
1416
1.97
1468
2.15
1900
1271
1.55
1331
1.73
1388
1.92
1442
2.11
1494
2.31
2000
1298
1.68
1358
1.87
1415
2.07
1468
2.27
---
---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181 and belt (part no. KR30AE041).
Table 20 – 558J*05
3 PHASE
4 TON VERTICAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
666
0.25
778
0.36
873
0.48
956
0.60
1031
0.72
1300
701
0.30
809
0.42
902
0.54
983
0.67
1057
0.80
1400
737
0.36
842
0.48
932
0.61
1012
0.75
1085
0.89
1500
774
0.42
875
0.55
962
0.69
1041
0.83
1112
0.98
1600
811
0.49
909
0.63
994
0.78
1071
0.93
1141
1.08
1700
849
0.57
943
0.72
1026
0.87
1101
1.03
1170
1.19
1800
887
0.65
978
0.81
1059
0.98
1133
1.14
1200
1.31
1900
926
0.75
1014
0.92
1092
1.09
1164
1.26
1231
1.44
2000
965
0.86
1050
1.03
1127
1.21
1197
1.39
1262
1.58
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
1200
1100
0.85
1165
0.98
1225
1.12
1282
1.26
1337
1.40
1300
1126
0.94
1189
1.07
1249
1.22
1306
1.36
1360
1.51
1400
1152
1.03
1215
1.17
1274
1.32
1330
1.48
1384
1.63
1500
1179
1.13
1241
1.28
1300
1.44
1355
1.60
1408
1.76
1600
1206
1.24
1268
1.40
1326
1.56
1381
1.73
1433
1.90
1700
1235
1.36
1295
1.52
1352
1.69
1407
1.87
1459
2.04
1800
1264
1.48
1323
1.66
1380
1.84
1434
2.02
1485
2.20
1900
1293
1.62
1352
1.80
1408
1.99
1461
2.17
1512
2.37
2000
1324
1.77
1381
1.96
1436
2.15
1489
2.34
---
---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181 and belt (part no. KR30AE041).
558J