Fan performance (cont.) – Bryant LEGACY 558J User Manual
Page 31
31
FAN PERFORMANCE (cont.)
Table 25 – 558J*07
3 PHASE
6 TON HORIZONTAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Field---Supplied Drive
1
Standard Static Option
1800
822
0.51
927
0.66
1018
0.82
1100
0.98
1174
1.15
1950
872
0.62
973
0.79
1061
0.95
1140
1.13
1213
1.31
2100
923
0.75
1019
0.92
1104
1.10
1182
1.29
1253
1.48
2250
974
0.90
1067
1.08
1149
1.27
1224
1.46
1294
1.66
2400
1026
1.06
1115
1.26
1195
1.46
1268
1.66
1336
1.87
2550
1079
1.25
1164
1.46
1241
1.67
1312
1.88
1379
2.10
2700
1132
1.46
1214
1.67
1289
1.90
1358
2.12
1422
2.35
2850
1186
1.69
1264
1.92
1336
2.15
1404
2.39
1467
2.63
3000
1240
1.94
1315
2.18
1385
2.43
1451
2.68
1512
2.93
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1800
1244
1.33
1308
1.51
1369
1.70
1427
1.90
1483
2.10
1950
1281
1.49
1345
1.68
1405
1.88
1462
2.09
1517
2.30
2100
1320
1.67
1382
1.87
1441
2.08
1498
2.29
1552
2.51
2250
1359
1.87
1420
2.08
1479
2.29
1534
2.51
1587
2.74
2400
1400
2.09
1460
2.31
1517
2.53
1572
2.76
1624
2.99
2550
1441
2.33
1500
2.55
1557
2.79
1610
3.03
1662
3.27
2700
1483
2.59
1541
2.83
1597
3.07
1650
3.32
1701
3.57
2850
1527
2.87
1583
3.12
1638
3.37
1690
3.63
---
---
3000
1571
3.18
1626
3.44
1680
3.70
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part no. KR11AZ002), motor pulley (part no. KR11HY191) and belt (part no. KR30AE042).
Table 26 – 558J*07
3 PHASE
6 TON VERTICAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Field---Supplied Drive
1
Standard Static Option
Medium Static Option
1800
907
0.63
1006
0.80
1092
0.97
1169
1.14
1239
1.32
1950
965
0.77
1060
0.95
1143
1.13
1218
1.32
1287
1.51
2100
1024
0.93
1115
1.12
1195
1.32
1268
1.52
1335
1.72
2250
1083
1.11
1170
1.32
1248
1.53
1319
1.74
1385
1.96
2400
1143
1.32
1227
1.54
1302
1.76
1371
1.99
1435
2.22
2550
1203
1.55
1284
1.78
1357
2.02
1424
2.26
1487
2.50
2700
1264
1.81
1342
2.06
1412
2.31
1478
2.56
1539
2.82
2850
1326
2.09
1400
2.36
1469
2.62
1532
2.89
1592
3.16
3000
1387
2.41
1459
2.69
1525
2.97
1587
3.25
1646
3.53
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
1800
1304
1.51
1365
1.69
1422
1.88
1477
2.08
1528
2.28
1950
1350
1.71
1410
1.91
1467
2.11
1520
2.31
1572
2.52
2100
1398
1.93
1457
2.14
1512
2.35
1565
2.57
1616
2.79
2250
1446
2.18
1504
2.40
1559
2.62
1611
2.85
1661
3.09
2400
1496
2.45
1552
2.68
1606
2.92
1658
3.16
1707
3.40
2550
1546
2.75
1601
2.99
1654
3.24
1705
3.50
---
---
2700
1597
3.07
1651
3.33
1703
3.59
---
---
---
---
2850
1648
3.43
1702
3.70
---
---
---
---
---
---
3000
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part no. KR11AZ002), motor pulley (part no. KR11HY191) and belt (part no. KR30AE042).
558J