Bryant LEGACY 558J User Manual
Page 44
44
C08054
Fig. 13 -- Typical Power Diagram
LEGEND
C
--- Contactor, compressor
CAP
--- Capacitor
CB
--- Circuit breaker
CCH
--- Crankcase heater
COMP
--- Compressor motor
DDC
--- Direct digital control
FU
--- Fuse
GND
--- Ground
HPS
--- High pressure switch
IAQ
--- Indoor air quality sensors
IFC
--- Indoor fan motor
IFM
--- Indoor fan motor
LA
--- Low ambient lockout
LPS
--- Low pressure switch
LSM
--- Limit switch (manual reset)
MGV
--- Main gas valve
OAT
--- Outdoor air temp sensor
OFM
--- Outdoor fan motor
OLR
--- Overload relay
PL
--- Plug assembly
POT
--- Potentiometer
PMR
--- Phase monitor relay
QT
--- Quadruple terminal
R
--- Relay
RAT
--- Return air temp sensor
SAT
--- Supply air temp sensor
TDR
--- Time delay relay
TRAN
--- Transformer
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
2. Compressor and fan motors are thermally protected. Three phase motors are protected against primary single phasing
conditions.
3. On 208/230V units, transformer is wired for 230V. If unit is to be run with 208V power supply, disconnect black wire from
230V tap and connect to 200V tap. 230V, 200V taps on transformer do not appear on 575V transformer and 575V tap does
not appear on 208/23/460V transformer.
4. Use copper, copper clad, aluminum or aluminum connectors.
5. Use copper conductor only.
558J