Fan performance (cont.) – Bryant LEGACY 558J User Manual
Page 29
29
FAN PERFORMANCE (cont.)
Table 21 – 558J*06
1 PHASE
5 TON HORIZONTAL SUPPLY
CFM
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Field---Supplied Drive
1
Standard Static Option
1500
724
0.33
837
0.45
937
0.59
1028
0.74
1111
0.91
1625
765
0.40
873
0.53
969
0.67
1056
0.83
1137
1.00
1750
806
0.48
909
0.61
1002
0.76
1087
0.92
1165
1.10
1875
849
0.57
947
0.71
1036
0.86
1118
1.03
1195
1.21
2000
892
0.67
986
0.82
1072
0.98
1151
1.15
1226
1.33
2125
935
0.79
1025
0.94
1108
1.11
1185
1.29
1258
1.47
2250
980
0.92
1066
1.08
1146
1.25
1220
1.43
---
---
2375
1024
1.06
1107
1.23
1184
1.41
---
---
---
---
2500
1069
1.22
1149
1.39
---
---
---
---
---
---
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1188
1.09
1261
1.29
1330
1.49
---
---
---
---
1625
1213
1.18
1284
1.38
---
---
---
---
---
---
1750
1239
1.28
1309
1.49
---
---
---
---
---
---
1875
1267
1.40
---
---
---
---
---
---
---
---
2000
---
---
---
---
---
---
---
---
---
---
2125
---
---
---
---
---
---
---
---
---
---
2250
---
---
---
---
---
---
---
---
---
---
2375
---
---
---
---
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY171) and belt (part number KR30AE039).
Table 22 – 558J*06
1 PHASE
5 TON VERTICAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
1500
790
0.40
897
0.53
991
0.68
1075
0.83
1152
1.00
1625
837
0.48
940
0.62
1030
0.77
1112
0.94
1187
1.11
1750
885
0.58
983
0.73
1070
0.89
1150
1.06
1223
1.24
1875
934
0.69
1027
0.85
1112
1.01
1189
1.19
1260
1.38
2000
983
0.81
1073
0.98
1154
1.16
1229
1.34
---
---
2125
1033
0.95
1119
1.13
1198
1.31
1270
1.50
---
---
2250
1084
1.11
1166
1.29
1242
1.49
---
---
---
---
2375
1134
1.28
1214
1.48
---
---
---
---
---
---
2500
1185
1.48
---
---
---
---
---
---
---
---
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1224
1.18
1291
1.36
---
---
---
---
---
---
1625
1257
1.30
1323
1.49
---
---
---
---
---
---
1750
1292
1.43
---
---
---
---
---
---
---
---
1875
---
---
---
---
---
---
---
---
---
---
2000
---
---
---
---
---
---
---
---
---
---
2125
---
---
---
---
---
---
---
---
---
---
2250
---
---
---
---
---
---
---
---
---
---
2375
---
---
---
---
---
---
---
---
---
---
2500
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY171) and belt (part number KR30AE039).
558J