FAN PERFORMANCE (cont.)
Table 17 – 558J*05
1 PHASE
4 TON HORIZONTAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
643
0.23
762
0.35
860
0.46
944
0.58
1020
0.71
1300
674
0.28
791
0.40
887
0.52
970
0.65
1045
0.78
1400
706
0.33
820
0.45
914
0.59
997
0.72
1071
0.86
1500
738
0.38
849
0.52
942
0.66
1024
0.80
1097
0.95
1600
771
0.44
879
0.59
971
0.74
1051
0.89
1124
1.04
1700
804
0.51
910
0.66
1000
0.82
1079
0.98
1151
1.14
1800
837
0.59
941
0.75
1029
0.91
1107
1.08
---
---
1900
871
0.67
972
0.84
1059
1.02
1136
1.19
---
---
2000
906
0.76
1004
0.94
1089
1.12
---
---
---
---
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field---Supplied Drive
1
1200
1089
0.84
1153
0.98
1212
1.12
---
---
---
---
1300
1114
0.92
1177
1.06
---
---
---
---
---
---
1400
1139
1.01
1202
1.15
---
---
---
---
---
---
1500
1164
1.10
---
---
---
---
---
---
---
---
1600
1190
1.20
---
---
---
---
---
---
---
---
1700
---
---
---
---
---
---
---
---
---
---
1800
---
---
---
---
---
---
---
---
---
---
1900
---
---
---
---
---
---
---
---
---
---
2000
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
Table 18 – 558J*05
1 PHASE
4 TON VERTICAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
666
0.25
778
0.36
873
0.48
956
0.60
1031
0.72
1300
701
0.30
809
0.42
902
0.54
983
0.67
1057
0.80
1400
737
0.36
842
0.48
932
0.61
1012
0.75
1085
0.89
1500
774
0.42
875
0.55
962
0.69
1041
0.83
1112
0.98
1600
811
0.49
909
0.63
994
0.78
1071
0.93
1141
1.08
1700
849
0.57
943
0.72
1026
0.87
1101
1.03
1170
1.19
1800
887
0.65
978
0.81
1059
0.98
1133
1.14
---
---
1900
926
0.75
1014
0.92
1092
1.09
---
---
---
---
2000
965
0.86
1050
1.03
---
---
---
---
---
---
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
Field---Supplied Drive
1
1200
1100
0.85
1165
0.98
1225
1.12
---
---
---
---
1300
1126
0.94
1189
1.07
---
---
---
---
---
---
1400
1152
1.03
1215
1.17
---
---
---
---
---
---
1500
1179
1.13
---
---
---
---
---
---
---
---
1600
1206
1.24
---
---
---
---
---
---
---
---
1700
1235
1.36
---
---
---
---
---
---
---
---
1800
1264
1.48
---
---
---
---
---
---
---
---
1900
1293
1.62
---
---
---
---
---
---
---
---
2000
1324
1.77
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).