beautypg.com

Fan performance – Bryant LEGACY 558J User Manual

Page 25

background image

25

FAN PERFORMANCE

Table 13 – 558J*04

1 PHASE

3 TON HORIZONTAL SUPPLY

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Field---Supplied Drive

1

Standard Static Option

Medium Static Option

900

554

0.14

681

0.22

783

0.32

870

0.42

947

0.53

975

575

0.16

701

0.25

801

0.35

888

0.45

965

0.57

1050

597

0.18

721

0.28

821

0.38

906

0.49

983

0.61

1125

620

0.21

741

0.31

840

0.42

925

0.54

1001

0.66

1200

643

0.23

762

0.35

860

0.46

944

0.58

1020

0.71

1275

666

0.27

784

0.38

880

0.50

964

0.63

1039

0.76

1350

690

0.30

805

0.42

900

0.55

983

0.68

1058

0.82

1425

714

0.34

827

0.47

921

0.60

1003

0.74

1077

0.88

1500

738

0.38

849

0.52

942

0.66

1024

0.80

1097

0.95

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

Field---Supplied Drive

2

900

1017

0.64

1082

0.76

1143

0.88

1200

1.01

1254

1.14

975

1035

0.68

1100

0.81

1160

0.93

1217

1.07

1271

1.20

1050

1053

0.73

1117

0.86

1177

0.99

1234

1.13

---

---

1125

1071

0.78

1135

0.92

1195

1.05

1251

1.19

---

---

1200

1089

0.84

1153

0.98

1212

1.12

---

---

---

---

1275

1107

0.90

1171

1.04

1230

1.19

---

---

---

---

1350

1126

0.96

1189

1.11

---

---

---

---

---

---

1425

1145

1.03

1208

1.18

---

---

---

---

---

---

1500

1164

1.10

---

---

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 23.

Boldface indicates field---supplied drive is required.

1. Recommend using field---supplied fan pulley (part number KR11AZ712) and belt (part number KR30AE039).
2. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).

Table 14 – 558J*04

1 PHASE

3 TON VERTICAL SUPPLY

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Field---Supplied Drive

1

Standard Static Option

Medium Static Option

900

566

0.14

690

0.23

791

0.32

879

0.42

957

0.52

975

590

0.17

711

0.26

811

0.36

897

0.46

975

0.57

1050

615

0.19

733

0.29

831

0.39

916

0.50

993

0.62

1125

640

0.22

755

0.33

851

0.43

936

0.55

1012

0.67

1200

666

0.25

778

0.36

873

0.48

956

0.60

1031

0.72

1275

692

0.29

802

0.41

894

0.53

976

0.65

1051

0.78

1350

719

0.33

825

0.45

916

0.58

997

0.71

1071

0.84

1425

746

0.37

850

0.50

939

0.63

1019

0.77

1091

0.91

1500

774

0.42

875

0.55

962

0.69

1041

0.83

1112

0.98

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

Field---Supplied Drive

2

900

1029

0.63

1095

0.75

1157

0.86

1216

0.99

1272

1.11

975

1046

0.68

1112

0.80

1174

0.92

1232

1.05

1287

1.18

1050

1064

0.73

1129

0.86

1190

0.98

1248

1.11

---

---

1125

1082

0.79

1147

0.92

1208

1.05

1265

1.18

---

---

1200

1100

0.85

1165

0.98

1225

1.12

---

---

---

---

1275

1119

0.91

1183

1.05

1243

1.19

---

---

---

---

1350

1139

0.98

1202

1.12

---

---

---

---

---

---

1425

1159

1.05

1221

1.20

---

---

---

---

---

---

1500

1179

1.13

---

---

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 23.

Boldface indicates field---supplied drive is required.

1. Recommend using field---supplied fan pulley (part number KR11AZ712) and belt (part number KR30AE039).