beautypg.com

Sequence of operation – Bryant LEGACY 558J User Manual

Page 46

background image

46

SEQUENCE OF OPERATION

General

The sequence below describes the sequence of operation

for an electro--mechanical unit with and without a factory

installed EconoMi$er IV (called “economizer” in this

sequence). For information regarding a direct digital

controller,

see

the

start--up,

operations,

and

troubleshooting manual for the applicable controller.

Electro--mechanical units with no economizer

Cooling —

When the thermostat calls for cooling, terminals G and Y1

are energized. As a result, the indoor--fan contactor (IFC)

and the compressor contactor (C1) are energized, causing

the indoor--an motor (IFM), compressor #1, and outdoor

fan to start. If the unit has 2 stages of cooling, the

thermostat will additionally energize Y2. The Y2 signal

will energize compressor contactor #2 (C2), causing

compressor #2 to start. Regardless of the number of

stages, the outdoor--an motor runs continuously while unit

is cooling.
Heating
NOTE
: The 558J is sold as cooling only. If electric
heaters are required, use only factory--approved electric
heaters. They will operate as described below.
Units have either 1 or 2 stages of electric heat. When the

thermostat calls for heating, power is applied to the W1

terminal at the unit. The unit control will energize the

indoor fan contactor and the first stage of electric heat. On

units with two--stage heating, when additional heating is

required, the second stage of electric heat (if equipped)

will be energized when power is applied at the W2

terminal on the unit.

Electro--mechanical units with an economizer

Cooling —

When free cooling is not available, the compressors will

be controlled by the zone thermostat. When free cooling is

available, the outdoor--air damper is modulated by the

EconoMi$er IV control to provide a 50_F (10_C) to 55_F

(13_C) mixed--air temperature into the zone. As the mixed

air temperature fluctuates above 55_F (13_C) or below

50_F (10_C) dampers will be modulated (open or close)

to bring the mixed--air temperature back within control. If

mechanical cooling is utilized with free cooling, the

outdoor--air damper will maintain its current position at

the time the compressor is started. If the increase in

cooling capacity causes the mixed--air temperature to drop

below 45_F (7_C), then the outdoor--air damper position

will be decreased to the minimum position. If the

mixed--air temperature continues to fall, the outdoor--air

damper will close. Control returns to normal once the

mixed--air temperature rises above 48_F (9_C). The

power exhaust fans will be energized and de--energized, if

installed, as the outdoor--air damper opens and closes.

If field--installed accessory CO2 sensors are connected to

the EconoMi$er IV control, a demand controlled

ventilation strategy will begin to operate. As the CO2

level in the zone increases above the CO2 set point, the

minimum position of the damper will be increased

proportionally. As the CO2 level decreases because of the

increase in fresh air, the outdoor--air damper will be

proportionally closed. For EconoMi$er IV operation, there

must be a thermostat call for the fan (G). If the unit is

occupied and the fan is on, the damper will operate at

minimum position. Otherwise, the damper will be closed.

When the EconoMi$er IV control is in the occupied mode

and a call for cooling exists (Y1 on the thermostat), the

control will first check for indoor fan operation. If the fan

is not on, then cooling will not be activated. If the fan is

on, then the control will open the EconoMi$er IV damper

to the minimum position.

On the initial power to the EconoMi$er IV control, it will

take the damper up to 2 1/2 minutes before it begins to

position itself. After the initial power--up, further changes

in damper position can take up to 30 seconds to initiate.

Damper movement from full closed to full open (or vice

versa) will take between 1 1/2 and 2 1/2 minutes. If free

cooling can be used as determined from the appropriate

changeover command (switch, dry bulb, enthalpy curve,

differential dry bulb, or differential enthalpy), then the

control will modulate the dampers open to maintain the

mixed--air temperature set point at 50_F (10_C) to 55_F

(13_C). If there is a further demand for cooling (cooling

second stage -- Y2 is energized), then the control will

bring on compressor stage 1 to maintain the mixed--air

temperature set point. The EconoMi$er IV damper will be

open at maximum position. EconoMi$er IV operation is

limited to a single compressor.
Heating

The sequence of operation for the heating is the same as

an electromechanical unit with no economizer. The only

difference is how the economizer acts. The economizer

will stay at the Economizer Minimum Position while the

evaporator fan is operating. The outdoor--air damper is

closed when the indoor fan is not operating.

558J