beautypg.com

Fan performance (cont.), Table 27 – pulley adjustment – Bryant LEGACY 558J User Manual

Page 32

background image

32

FAN PERFORMANCE (cont.)

Table 27 – PULLEY ADJUSTMENT

UNIT

MOTOR/DRIVE

COMBO

MOTOR PULLEY TURNS OPEN

0.0

0.5

1.0

1.5

2.0

2.5

3.0

3.5

4.0

4.5

5.0

04

1p

ha

se

Standard Static

854

825

795

766

736

707

678

648

619

589

560

Medium Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

High Static

---

---

---

---

---

---

---

---

---

---

---

3p

ha

se

Standard Static

854

825

795

766

736

707

678

648

619

589

560

Medium Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

High Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

05

1p

ha

se

Standard Static

854

825

795

766

736

707

678

648

619

589

560

Medium Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

High Static

---

---

---

---

---

---

---

---

---

---

---

3p

ha

se

Standard Static

854

825

795

766

736

707

678

648

619

589

560

Medium Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

High Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

06

1p

ha

se

Standard Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

Medium Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

High Static

---

---

---

---

---

---

---

---

---

---

---

3p

ha

se

Standard Static

1175

1135

1094

1054

1013

973

932

892

851

811

770

Medium Static

1466

1423

1380

1337

1294

1251

1207

1164

1121

1078

1035

High Static

1687

1649

1610

1572

1533

1495

1457

1418

1380

1341

1303

07

3p

ha

se

Standard Static

1457

1419

1380

1342

1303

1265

1227

1188

1150

1111

1073

Medium Static

1518

1484

1449

1415

1380

1346

1311

1277

1242

1208

1173

High Static

1788

1757

1725

1694

1662

1631

1600

1568

1537

1505

1474

NOTE: Do not adjust pulley further than 5 turns open.

--- Factory settings

558J