Curbs & weights dimensions -- chassis 1, Table 7 – base unit dimensions -- chassis 1 – Bryant LEGACY 558J User Manual
Page 16
16
CURBS & WEIGHTS DIMENSIONS -- CHASSIS 1
Corner
D
Corner
A
Corner
B
Corner
C
6 1/8”
7”
10 1/2”
19 1/2”
22”
16 1/4”
11 3/8”
C08001
21 1/4”
19 1/2”
33 3/8”
16”
74 3/8”
J
4 5/8”
K
6 5/8”
C08000
Table 7 – BASE UNIT DIMENSIONS -- CHASSIS 1
UNIT
OPERATING
WGT (LB)
SHIPPING
WGT (LB)
J
CORNER WEIGHTS (LB)
CENTER OF GRAVITY (IN)
A
B
C
D
X
Y
HEIGHT
04
438
475
33 5/16”
108
115
110
104
38
23
17 1/4
05
494
530
33 5/16”
122
130
125
117
38
23
17 1/2
06
524
560
33 5/16”
130
138
132
124
38
23
17 3/4
07
607
645
41 5/16”
150
160
153
144
38
23
20 3/4
NOTES:
1. If one side has at least 36” (914mm) of clearance, the
opposite side can be reduced to 12” (305mm). Make
sure to plan for OA handler, if equipped.
2. Clearance of 0” requires use of an alternate drain con-
nection.
3. Maintain 36” (914mm) between control box and groun-
ded surface or 42” (1067mm) between control box and
ungrounded surfaces (concrete or block wall).
4. Keep combustible material at 36” (914mm) away from
the flue discharge. Accessory flue discharge deflector
may allow smaller clearance.
5. Units shown with optional economizer.
6. Local codes and jurisdictions may prevail.
7. Height is measured from bottom of base rail.
558J