beautypg.com

Fan performance (cont.) – Bryant LEGACY 558J User Manual

Page 30

background image

30

FAN PERFORMANCE (cont.)

Table 23 – 558J*06

3 PHASE

5 TON HORIZONTAL SUPPLY

CFM

Available External Static Pressure (in. wg)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Field---Supplied Drive

1

Standard Static Option

1500

724

0.33

837

0.45

937

0.59

1028

0.74

1111

0.91

1625

765

0.40

873

0.53

969

0.67

1056

0.83

1137

1.00

1750

806

0.48

909

0.61

1002

0.76

1087

0.92

1165

1.10

1875

849

0.57

947

0.71

1036

0.86

1118

1.03

1195

1.21

2000

892

0.67

986

0.82

1072

0.98

1151

1.15

1226

1.33

2125

935

0.79

1025

0.94

1108

1.11

1185

1.29

1258

1.47

2250

980

0.92

1066

1.08

1146

1.25

1220

1.43

1291

1.63

2375

1024

1.06

1107

1.23

1184

1.41

1256

1.60

1325

1.79

2500

1069

1.22

1149

1.39

1223

1.58

1293

1.77

1360

1.98

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

1500

1188

1.09

1261

1.29

1330

1.49

1395

1.71

1457

1.95

1625

1213

1.18

1284

1.38

1352

1.59

1416

1.81

1478

2.04

1750

1239

1.28

1309

1.49

1375

1.70

1439

1.92

1499

2.16

1875

1267

1.40

1335

1.60

1400

1.82

1462

2.04

1522

2.28

2000

1296

1.53

1363

1.74

1427

1.95

1488

2.18

1546

2.42

2125

1326

1.67

1392

1.88

1454

2.11

1514

2.34

1571

2.58

2250

1358

1.83

1421

2.05

1483

2.27

1541

2.51

1598

2.75

2375

1390

2.00

1452

2.22

1512

2.45

1570

2.69

1625

2.94

2500

1424

2.19

1484

2.42

1543

2.65

1599

2.89

1654

3.15

NOTE: For more information, see General Fan Performance Notes on page 23.

Boldface indicates field---supplied drive is required.

1. Recommend using field---supplied motor pulley (part number KR11HY191) and belt (part number KR30AE042).

Table 24 – 558J*06

3 PHASE

5 TON VERTICAL SUPPLY

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

0.2

0.4

0.6

0.8

1.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Standard Static Option

1500

790

0.40

897

0.53

991

0.68

1075

0.83

1152

1.00

1625

837

0.48

940

0.62

1030

0.77

1112

0.94

1187

1.11

1750

885

0.58

983

0.73

1070

0.89

1150

1.06

1223

1.24

1875

934

0.69

1027

0.85

1112

1.01

1189

1.19

1260

1.38

2000

983

0.81

1073

0.98

1154

1.16

1229

1.34

1299

1.53

2125

1033

0.95

1119

1.13

1198

1.31

1270

1.50

1338

1.71

2250

1084

1.11

1166

1.29

1242

1.49

1312

1.69

1379

1.89

2375

1134

1.28

1214

1.48

1287

1.68

1355

1.89

1420

2.10

2500

1185

1.48

1262

1.68

1333

1.89

1399

2.10

1462

2.33

CFM

AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)

1.2

1.4

1.6

1.8

2.0

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

Medium Static Option

1500

1224

1.18

1291

1.36

1354

1.56

1414

1.77

1472

1.98

1625

1257

1.30

1323

1.49

1385

1.69

1445

1.90

1501

2.12

1750

1292

1.43

1356

1.63

1418

1.83

1476

2.05

1532

2.27

1875

1327

1.57

1391

1.78

1451

1.99

1509

2.21

1564

2.44

2000

1364

1.74

1427

1.95

1486

2.17

1542

2.39

1596

2.63

2125

1402

1.92

1463

2.13

1521

2.36

1577

2.59

1630

2.83

2250

1441

2.11

1501

2.34

1558

2.57

1612

2.81

---

---

2375

1481

2.33

1539

2.56

1595

2.80

---

---

---

---

2500

1522

2.56

1579

2.80

---

---

---

---

---

---

NOTE: For more information, see General Fan Performance Notes on page 23.

Boldface indicates field---supplied drive is required.

1. Recommend using field---supplied motor pulley (part number KR11HY191) and belt (part number KR30AE042).

558J