Fan performance (cont.) – Bryant LEGACY 558J User Manual
Page 30
30
FAN PERFORMANCE (cont.)
Table 23 – 558J*06
3 PHASE
5 TON HORIZONTAL SUPPLY
CFM
Available External Static Pressure (in. wg)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Field---Supplied Drive
1
Standard Static Option
1500
724
0.33
837
0.45
937
0.59
1028
0.74
1111
0.91
1625
765
0.40
873
0.53
969
0.67
1056
0.83
1137
1.00
1750
806
0.48
909
0.61
1002
0.76
1087
0.92
1165
1.10
1875
849
0.57
947
0.71
1036
0.86
1118
1.03
1195
1.21
2000
892
0.67
986
0.82
1072
0.98
1151
1.15
1226
1.33
2125
935
0.79
1025
0.94
1108
1.11
1185
1.29
1258
1.47
2250
980
0.92
1066
1.08
1146
1.25
1220
1.43
1291
1.63
2375
1024
1.06
1107
1.23
1184
1.41
1256
1.60
1325
1.79
2500
1069
1.22
1149
1.39
1223
1.58
1293
1.77
1360
1.98
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1188
1.09
1261
1.29
1330
1.49
1395
1.71
1457
1.95
1625
1213
1.18
1284
1.38
1352
1.59
1416
1.81
1478
2.04
1750
1239
1.28
1309
1.49
1375
1.70
1439
1.92
1499
2.16
1875
1267
1.40
1335
1.60
1400
1.82
1462
2.04
1522
2.28
2000
1296
1.53
1363
1.74
1427
1.95
1488
2.18
1546
2.42
2125
1326
1.67
1392
1.88
1454
2.11
1514
2.34
1571
2.58
2250
1358
1.83
1421
2.05
1483
2.27
1541
2.51
1598
2.75
2375
1390
2.00
1452
2.22
1512
2.45
1570
2.69
1625
2.94
2500
1424
2.19
1484
2.42
1543
2.65
1599
2.89
1654
3.15
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY191) and belt (part number KR30AE042).
Table 24 – 558J*06
3 PHASE
5 TON VERTICAL SUPPLY
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
1500
790
0.40
897
0.53
991
0.68
1075
0.83
1152
1.00
1625
837
0.48
940
0.62
1030
0.77
1112
0.94
1187
1.11
1750
885
0.58
983
0.73
1070
0.89
1150
1.06
1223
1.24
1875
934
0.69
1027
0.85
1112
1.01
1189
1.19
1260
1.38
2000
983
0.81
1073
0.98
1154
1.16
1229
1.34
1299
1.53
2125
1033
0.95
1119
1.13
1198
1.31
1270
1.50
1338
1.71
2250
1084
1.11
1166
1.29
1242
1.49
1312
1.69
1379
1.89
2375
1134
1.28
1214
1.48
1287
1.68
1355
1.89
1420
2.10
2500
1185
1.48
1262
1.68
1333
1.89
1399
2.10
1462
2.33
CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.2
1.4
1.6
1.8
2.0
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1224
1.18
1291
1.36
1354
1.56
1414
1.77
1472
1.98
1625
1257
1.30
1323
1.49
1385
1.69
1445
1.90
1501
2.12
1750
1292
1.43
1356
1.63
1418
1.83
1476
2.05
1532
2.27
1875
1327
1.57
1391
1.78
1451
1.99
1509
2.21
1564
2.44
2000
1364
1.74
1427
1.95
1486
2.17
1542
2.39
1596
2.63
2125
1402
1.92
1463
2.13
1521
2.36
1577
2.59
1630
2.83
2250
1441
2.11
1501
2.34
1558
2.57
1612
2.81
---
---
2375
1481
2.33
1539
2.56
1595
2.80
---
---
---
---
2500
1522
2.56
1579
2.80
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 23.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY191) and belt (part number KR30AE042).
558J