Winland Electronics EA400 User Manual
Page 51

D-011-0093
49
Sensor Type/Connection:
• Temperature:
• Humidity:
• Water Presence:
2-wire, 18-22AWG; maximum 304 m (1000 ft.) cabling length
3-wire, 18-22AWG; maximum 304 m (1000 ft.) cabling length
2-wire, 18-22AWG; maximum 304 m (1000 ft.) cabling length
Minimum Span Between High and
Low Limits
• 4° C (° F)
• 4% RH
Relay Outputs
• (2) Form C with 3-terminal
NC/COM/NO connections
corresponding to Zones 1
and 2.
• (1) Form C with 3-terminal
NC/COM/NO used for Aux
Output alarm (combined
OR function of Zones 1 and
2).
• (4) Form C with 3-terminal
NC/COM/NO connections
corresponding to Zones 1
through 4.
• (1) Form C with 3-terminal
NC/COM/NO used for Aux
Output alarm (combined OR
function of Zones 1 through
4).
Relay Contact Ratings
1 A at 30 VDC
Relay Logic
User configurable for:
• Alarm= energized coil, or
• Alarm= de-energized coil
Each zone individually configurable.
Display
Multiple icon Liquid Crystal Display (LCD)
Specifications — continued
Item
EA200
EA400
Winland_English.fm Page 49 Wednesday, July 5, 2006 1:33 PM