SENSOR IN 3
EA200: Not available (blank position).
EA400: Input for Zone 3 external temperature, water, or humidity sensor.
SENSOR IN 4
EA200: Not available (blank position).
EA400: Input for Zone 4 external temperature, water, or humidity sensor.
WARNING: EA200 / EA400 relay outputs are intended only for use as low-voltage,
low-current alarm connections, and not for direct switching or control of AC-mains
powered loads. Additionally, local codes may further dictate or limit the types of
loads and associated wiring to be used with the low-current Form C relay outputs
used with the EA200 / EA400. Connecting AC-mains type circuits to the EA200 /
EA400 may result in an electric shock and/or fire hazard.
CAUTION: Do not connect a load to the AUX OUT or OUTPUT 1 through OUTPUT 4
relay outputs that exceeds limitations stated in the Specifications section of this
manual. Loads exceeding the specified limitations may damage EA200 / EA400, or
result in improper or unreliable operation.
AUX OUT
Form C relay output that activates upon any alarm. Allows for a single output to an
alarm panel. This relay cannot be configured for energized or de-energized.
OUTPUT 1
EA200: Form C relay alarm output for built-in sensor (Zone 1).
EA400: Form C relay alarm output for Zone 1.
OUTPUT 2
EA200: Form C relay alarm output for external sensor (Zone 2).
EA400: Form C relay alarm output for Zone 2.
EA200 / EA400 Connectors — continued