Note: If a Zone is not to be used, set the Zone to Disabled (

). If an unconnected

Zone is not disabled, nuisance alarms may occur. Proceed to step 1 above to

program other Zones.

Note: All sensor selections (other than Disabled) require that the Zone be properly

connected to the sensor type entered during programming.

Note: The sequencing shown here assumes using the INCREASE KEY to scroll

through the choices. The opposite sequence occurs using the DECREASE

key.

4.

Depending on the monitoring function selected above, proceed as follows:

If Temperature function ( ) or Humidity function ( ) was selected, go to

step 5.

If Water Detection function ( ) was selected, go to step 8.

5.

When the display shown below appears, enter the High limit desired to be

programmed (flashing) by using the INCREASE or DECREASE keys to scroll to the

desired value, then press the ENTER key.

6.

Enter the Low limit desired to be programmed (flashing) by using the INCREASE or

DECREASE keys to scroll to the desired value, and then press the ENTER key.