beautypg.com

NOVUS Controller N1100 User Manual

Page 4

background image

Controller N1100

NOVUS AUTOMATION

4/8

TYPE

PROMPT

ACTION

Disabled

off

off

off

off

No active alarm. This output can be used as a
digital output to be set by the serial
communication.

Sensor Break

(input Error)

ierr

ierr

ierr

ierr

Alarm will be ON if PV sensor breaks, input
signal is out of range or Pt100 is shorted.

Event Alarm

(ramp and

Soak)

rs

rs

rs

rs

Can be activated at a specific segment of ramp
and soak program.

Detection

resistance fail

rfail

rfail

rfail

rfail

Detects a heater broken condition

Low Alarm

lo

lo

lo

lo

SPAn

PV

High Alarm

ki

ki

ki

ki

SPAn

PV

LOW

Differential

difl

difl

difl

difl

SV

PV

SV - SPAn

positive SPAn

SV

PV

SV - SPAn

negative SPAn

HIGH

Differential

difk

difk

difk

difk

SV

PV

SV + SPAn

positive SPAn

SV

PV

SV + SPAn

negative SPAn

Differential

dif

dif

dif

dif

SV

PV

SV + SPAn

SV - SPAn

positive SPAn

SV

PV

SV - SPAn

SV + SPAn

negative SPAn

Table 3 - Alarm functions

Where SPAn means “SPA1

SPA1

SPA1

SPA1”, “SPA2

SPA2

SPA2

SPA2”, “SPA2

SPA2

SPA2

SPA2” and “SPA4

SPA4

SPA4

SPA4”.

Minimum value

It is activated when the measured value is below the value defined in
the alarm Setpoint.

Maximum value

It is activated when the measured value is above the value defined in
the alarm Setpoint.

Differential (or Band)

In this function, the parameters “SPA1

SPA1

SPA1

SPA1”, “SPA2

SPA2

SPA2

SPA2” represent the PV

deviation as compared to the main SP.

In a positive deviation, the differential alarm will be triggered when
the measured value is out of the range defined in:

( SP – Deviation) and (SP + Deviation)

In a negative deviation, the differential alarm will be triggered when
the measured value is within the range defined above.

Minimum differential

It is activated when the measured value is below the value defined in.

(SP - Deviation)

Maximum differential

It is activated when the measured value is above the value defined in:

(SP + Deviation)

ALARM TIMER FUNCTIONS

Alarms 1 and 2 can be programmed to have timer functions. The 3
modes of operation are:

pulse

delayed actuation

oscillator

The desired function can be achieved programming the parameters
“A1t1

A1t1

A1t1

A1t1”, “A1t2

A1t2

A1t2

A1t2”, “A2t1

A2t1

A2t1

A2t1” and “A2t2

A2t2

A2t2

A2t2” (see Table 4).

The LEDs associated to the alarms will light when the alarm condition
is recognized, not following the actual state of the output, which may
be temporarily OFF because of the temporization.

ALARM INITIAL BLOCKING

The initial blocking option inhibits the alarm from being recognized if
an alarm condition is present when the controller is first energized.
The alarm will actuate only after the occurrence of a non alarm
condition followed by a new occurrence for the alarm.

The initial blocking is disabled for the sensor break alarm function.

ALARM

FUNCTION

T1

T2

ACTION

Normal

0

0

Alarm Event

Alarm

Output

Delayed

0

1 s to 6500 s

Alarm Event

Alarm

Output

T2

Pulse

1 s to 6500 s

0

Alarm Event

Alarm

Output

T1

Oscillator 1 s to 6500 s 1 s to 6500 s

Alarm Event

Alarm

Output
alarme

T1

T2

T1

Table 4 - Advanced Timer Alarm (for alarms 1 or 2)

SOFT START

Defines the time interval for the output to reach its maximum value
(100 %). The soft start value is programmed in “SfSt

SfSt

SfSt

SfSt”. See also

parameters “ovLL

ovLL

ovLL

ovLL” and “ovkL

ovkL

ovkL

ovkL”.

SQUARE ROOT EXTRACTION

Available when input type 19 is selected. The indicator displays the
square root of the current signal input applied to terminals 10 and 11.

REMOTE SETPOINT

The remote Setpoint (SP) is enabled by an external digital signal in
either I/O3, I/O4 or I/O5, when programmed with the code 8 (Select
remote SP input).

An external resistor shunt of 100

is required between the terminals

9 and 10, as shown in Figure 6.

ANALOG RETRANSMISSION OF PV AND SP

The analog output, when not used for control purposes, is available
for retransmitting the SV and SP values in 0-20 or 4-20 mA. This
analog output is electrically isolated from other inputs and outputs.

The analog output signal is scaleable, with the output range determined
by the values programmed in the parameters “SPLL

SPLL

SPLL

SPLL” and “SPkL

SPkL

SPkL

SPkL”.

To obtain a voltage output, connect a resistor shunt to the current
output terminals (terminal 7 and 8).