E pr – NOVUS N2020 Controller User Manual

Page 4

background image

N2020 Controller

NOVUS AUTOMATION

4/7

START-UP
Upon the energizing, the controller shows the number of its software
version in the first 3 seconds. Then, it shows the process variable
value (PV) measured (temperature) on the upper display. The SP
value is showed on the lower display. This is the Indication Screen.
To operate in a process, the controller is required to be configured
previously. The configuration consists of a definition of each one of
the several parameters showed. The user must understand about the
importance of each parameter and, for each one, determine one valid
condition or a valid value.
The configuration parameters are together in affinity groups, known
as parameters cycles. The 6 levels of parameters are:

Operation / Tuning / Program / Alarms / Input / Calibration

The P key is used for accessing the parameters within a level:
Keeping the P key pressed, at every 2 seconds the controller jumps
to the next level of parameters, showing the first parameter of each
level:

PV > atvn > ptol > fva1 > type > pass > PV

To enter a particular level, simply release the “P” key when the first
parameter in that level is displayed. To walk through the parameters
in a level, press the “P” key with short strokes. To go back to the
previous parameter in a cycle, press

.

Each parameter is displayed with its prompt in the upper display and
value/condition in the lower display. Depending on the level of
parameter protection adopted, the parameter PASS precedes the
first parameter in the level where the protection becomes active. See
section CONFIGURATION PROTECTION.

DESCRIPTION OF THE PARAMETERS

OPERATION CYCLE

PV + SP

PV indication. The measured temperature value (PV)
is shown on the upper display (red). Control Setpoint
(SP) value is shown on the lower display (green).

(trl

Control Mode:

avto

- in automatic mode.

Man - in manual mode.

PV + MV

MV Value - The upper display shows PV value and
the lower display shows the percentage of MV
applied to the control output.
In automatic control mode, the MV value is showed
visually only. In manual control mode, the MV value
may be changed by the user. To differ this screen
from SP screen, the MV value blinks constantly.

E pr

Enable Program Selects the ramp and soak profile
program to be executed.

no

- the program is not executed

yes - the program is executed

With enabled outputs (RvN= YES), the program

starts right after the program is selected.

rvn

RUN Function. Enables control outputs and alarms.

YES

- Outputs enables.

NO

- Outputs not enabled.

TUNING CYCLE

Atvn

Auto-Tune: Enables the auto-tuning function for the
PID parameters (pb,ir, dt). Refer PID Parameters
Determination chapter in this manual and on website

www.novusautomation.com

for further details.

0ff

- Turned off. (no PID tuning)

Fast

- Execute the tuning in fast mode.

full

- Execute the tuning in accurate mode.

PB

Proportional Band - Value of the term P of the
control mode PID, in percentage of the maximum span

of the input type. Adjust of between 0 and 500.0 %.
When set to zero (0), control action is ON/OFF.

ir

Integral Rate - Value of the term I of the PID
algorithm, in repetitions per minute (Reset).
Adjustable between 0 and 99.99. Displayed only if
proportional band 0.

dt

Derivative Time - Value of the term D of the control
mode PID, in seconds. Adjustable between 0 and 300.0
seconds. Displayed only if proportional band 0.

(t

Cycle Time - Value in seconds in the PWM cycle
period of PID control. Adjustable between 0.5 and
100.0 seconds. Displayed only if proportional band 0.

kyst

Control Hysteresis - Is the hysteresis for ON/OFF
control (set in temperature units). This parameter is
only used when the controller is in ON/OFF mode

(Pb=0).

A(t

Action Control:
re

Control with Reverse Action. Appropriate for
heating. Turns control output on when PV is

below SP.

dir

Control with Direct Action. Appropriate for

cooling. Turns control output on when PV

is above SP.

sfst

SoftStart Function – Time interval, in seconds, in
which the control limits the speed of increase of the

control output (MV). From 0 to 9999 s.
Zero value ( 0 ) disables the SoftStart function.

0vt1

0vt2

0vt3

Assign functions to the output channels OUT1, OUT2
and OUT3:

Off

Not used.

(trl

Control output.

A1

Alarm 1 output.

A2

Alarm 2 output.

Lbd

Loop Break Detect Alarm.

0vt4

Operation mode of OUT4 output channel:

Off

Not used.

(trl

Digital control output (0 or 20 mA)

A1

Alarm output 1.(0 or 20 mA)

A2

Alarm output 2.(0 or 20 mA)

Lbd

Acts as the output for LB function

(.020

Analogical Control Output 0-20 mA

(.420

Analogical Control Output 4-20 mA

p.020

PV Retransmission 0-20 mA

p.420

PV Retransmission 4-20 mA

s.020

SP Retransmission 0-20 mA

s.420

PV Retransmission 4-20 mA