beautypg.com

Ramp and soak profile program, Auto tune, Calibration – NOVUS Controller N3000 User Manual

Page 7

background image

Controller N3000

NOVUS AUTOMATION

7/9

RAMP AND SOAK PROFILE PROGRAM

Seven ramp and soak profiles with up to 7 segments each can be

programmed. Longer profiles of up to 49 segments can be created by

linking 2 or more profiles.

SP

time

T1

T2

T3

T4

T5

SP0

SP1

SP2

SP3

SP4

SP5

SP6

SP7

T6

T7

SV

time

T1

T2

T3

SP0

SP1

SP2

SP3

T4=0

Figure 11 - Example of a complete ramp

and soak profile

Figure 12 - Example of a profile

with fewer segments. (T4 is set 0)

To execute a profile with fewer segments just program 0 (zero) for the

time intervals that follow the last segment to be executed.
The program tolerance “Ptol” defines the maximum deviation

between PV and SV for the execution of the profile. If this deviation is

exceeded, the program will be interrupted until the deviation falls to

within the tolerance band.
Programming 0 (zero) at this prompt disables the tolerance and the

profile execution will not to be halted even if PV does not follow SV

(time priority as opposed to SV priority).
The ramp and soak event function is used to activate alarms at any

segment of program 1. This applies only to program 1.

LINK OF PROGRAMS
It is possible to create a more complex program, with up to 49

segments, joining the seven programs. This way, at the end of a

program execution the controller immediately starts to run another one.
When a program is created, it must be defined in the “LP" screen

whether there will be or not another program.
To make the controller run a given program or many programs

continuously, it is only necessary to link a program to itself or the last

program to the first.

SV

time

T1

T2

T3

T4

T5

T1

T2

T3

T4

SP0

SP1

SP2

SP3

SP4

SP5 / SP0

SP1 SP2

SP3

SP4

Program 1

Program 2

Figure 13 - Example of two linked programs

EVENT ALARM
To enable this event function the alarms to be activated must be

selected for rS function and are programmed at the PE 0 to PE 5

prompts. The number to be programmed at the prompt defines the

alarms to be activated (Table 5).

CODE

ALARM 1

ALARM 2

ALARM 3

ALARM 4

0

1

X

2

X

3

X

X

4

X

5

X

X

6

X

X

7

X

X

X

8

X

9

X

X

10

X

X

11

X

X

X

12

X

X

13

X

X

X

14

X

X

X

15

X

X

X

X

Table 5 - Event codes for ramp and soak

To configure and execute a ramp and soak program:

Program the tolerance value, SV, time and event.

If any event alarm is required program the ramp and soak event

function.

Set the control mode to automatic.

Select ramp and soak program to be executed at prompt Prn (0 to 7)

Start control at the rvn prompt by selecting YES.

Before executing the program the controller waits for PV to reach the

first set point SP0 if PtoL is different than zero.
Should any power failure occur the controller resumes at the

beginning of the segment it currently is.

AUTO TUNE

During auto tune the process is controlled in ON/OFF mode at the

programmed SetPoint (SV). Depending on the process

characteristics large oscillations above and below SV may occur and

auto tuning may take several minutes to be concluded.
The recommended procedure is as follows:

Disable the control output at the rvn prompt by selecting NO.

Select auto mode operation at the Avto prompt by selecting YES.

Disable the ramp and soak function (select NO) and program a new

SV value other than the present PV (close to the desired set point).

Enable auto tuning at the Atvn prompt by selecting YES.

Enable the control output at the rvn prompt by selecting YES.

During the auto tune procedure the soft-start function will not operate

and large oscillations will be induced around the setpoint. Make sure

the process can accept these oscillations and fast control output

changes.
If auto tuning results are not satisfactory refer to Table 6 for manual

fine tuning procedure.

PARAMETER

RESPONSE

SOLUTION

Proportional Band

Slow Response

Decrease

Large Oscillation

Increase

Integral Rate

Slow Response

Incre ase

Large Oscillation

Decrease

Derivative Time

Slow Response or Instability

Decrease

Large Oscillation

Increase

Table 6 - Suggestions for manual tuning of PID parameters

CALIBRATION

INPUT CALIBRATION
All inputs are factory calibrated and recalibration should only be done

by qualified personnel. If you are not familiar with these procedures

do not attempt to calibrate this instrument. The calibration steps are:
a) Select the input type to be calibrated.
b) Set the desired upper and lower display limits.
c) At the input terminals inject an electrical signal corresponding to

a known indication value a little higher than the lower display

limit.

d) Select the inL( prompt. Through the

and

keys adjust

PV so that it matches the injected signal.

e) Inject a signal that corresponds to a value a little lower than the

upper limit of the display.

f) Select the ink( prompt. Through the

and

keys adjust

PV so that it matches the injected signal.

g) Repeat steps c) to f) to improve calibration.
Note: When verifications are proceded, note if the Pt100

excitation/activation current the calibrator requires is compliant to the

Pt100 excitation current used in this instrument: 0.750 mA.