beautypg.com

Installation / connection – NOVUS Controller N3000 User Manual

Page 3

background image

Controller N3000

NOVUS AUTOMATION

3/9

Alarm Function

T1

T2

ACTION

Normal

0

0

Alarm Event

Alarm

Output

Delayed

0

1s to 6500s

Alarm Event

Alarm

Output

T2

Pulse

1s to

6500s

0

Alarm Event

Alarm

Output

T1

Oscillator

1s to

6500s

1s to 6500s

Alarm Event

Alarm

Output

T1

T2

T1

Table 4 - Advanced Timer Alarm (for alarms 1 or 2)

ALARM INITIAL BLOCKING
The initial blocking option inhibits the alarm from being recognized if

an alarm condition is present when the controller is first energized.

The alarm will actuate only after the occurrence of a non alarm

condition followed by a new occurrence for the alarm.
The initial blocking is disabled for the sensor break alarm function.

SQUARE ROOT EXTRACTION
Available when input type 19 is selected. The indicator displays the

square root of the current signal input applied to terminals 22 and 24.

ANALOG RETRANSMISSION OF PV AND SP
The analog output, when not used for control purposes, is available

for retransmitting the SV and SP values in 0-20 or 4-20 mA. This

analog output is electrically isolated from other inputs and outputs.

The analog output signal is scaleable, with the output range

determined by the values programmed in the parameters “SPLL” and

“SPkL”. To obtain a voltage output, connect a resistor shunt to the

current output terminals (terminal 1 and 2).

SOFT START
Defines the time interval for the output to reach its maximum value

(100 %). The soft start value is programmed in “SfSt”. See also

parameters “ovLL” and “ovkL”.

INSTALLATION / CONNECTION

Insert the unit into the panel cut-out and slide the mounting clamp

from the rear to a firm grip at the panel.
All electrical connections are made to the screw terminals at the rear

of the controller. They accept wire sizes from 0.5 to 1.5 mm2 (16 to

22 AWG). The terminals should be tightened to a torque of 0.4 Nm

(3.5 lb in).
To minimize the pick-up of electrical noise, the low voltage DC

connections and the sensor input wiring should be routed away from

high-current power conductors. If this is impractical, use shielded

cables. In general, keep cable lengths to a minimum.

RECOMMENDATIONS FOR INSTALLATION
• Input signal wires should be laid out away from power lines and

preferably inside grounded conduits.

• Instrument mains (line) supply should be suitable for this purpose

and should not be shared.

• In controlling and monitoring applications, possible consequences

of any system failure must be considered in advance. The internal

alarm relay does not warrant total protection.

• Use of RC filters (47 R and 100 nF, serial) are highly

recommended when driving solenoids, contactor coils or other

inductive loads.

Figure 1 – Back panel terminals

POWER WIRING

If high voltage is

applied to a low

voltage input,

irreversible damage

will occur

Figure 2 – High and Low Voltage AC power wiring

INPUT CONNECTIONS

Thermocouple and Voltage (Volts and mV) input connect as in

Figure 3.

Figure 3 – T/C and Voltage

wiring

Figura 4 – Pt100 wiring with

three conductors

RTD (Pt100)

Figure 4 shows the Pt100 wiring, for 3 conductors. Terminals 10, 11 and 12

must have the same wire resistance for proper cable length compensation.

For 2 wire Pt100, short circuit terminals 10 and 11.

Figura 5 – connection of 4-20 mA

Figura 6 – Connection of 5 Vdc

4-20 mA:
Refer to Figure 5. (The controller provides an internal electronic

shunt for the input current. No changes in the circuit are necessary).

Alarm and output connection
When I/O channels are set up as output channels, they must have

their capacity respected, according do specifications.

Remote setpoint:
The remote Setpoint (SP) is enabled by an external digital signal in

either I/O5 or I/O6, when programmed with the code 8 (Select remote

SP input).An external resistor shunt of 100  is required betwee

n the

terminals 7 and 8.

DIGITAL INPUT