Details about some registers, Registers 0 and 1 - serial number, Register 2 – firmware version – NOVUS AirGate-GPRS User Manual
Page 28: Registers 5 to 14 – value of remote channel, Registers 31 to 45 – sim card identification, Register 46 – gsm signal level, Register 51 – status 1, Register 52 – status 2
AirGate-GPRS
NOVUS AUTOMATION
28/29
Address
Description
Minimum
Maximum
R/W
Mnemonic
SuperView
46
Current level of GSM signal, in dBm
-999
0
R
SignalLevel
51
Status 1
-32768
32767
R
Status1
52
Status 2
-32768
32767
R
Status2
DETAILS ABOUT SOME REGISTERS
REGISTERS 0 AND 1 - SERIAL NUMBER
Device serial number. Both registers together make up the serial number of the equipment, i.e., it should be treated as a
32-bit number.
REGISTER 2 – FIRMWARE VERSION
States the version of firmware of the device, as shown below:
If the version is “1.00” it will read the value as “100”. If the version is "2,04" it will read it as "204".
REGISTERS 3 AND 4 – VALUE OF THE ANALOG/DIGITAL CHANNEL
States the value of the respective input channel, according to the configuration. The value will be multiplied by a factor of
10, depending on the number of configured decimal points. Example: Value of 31.78 will be read as 3178.
REGISTERS 5 TO 14 – VALUE OF REMOTE CHANNEL
States the value of the respective remote channel, as show in the configuration. The value will be multiplied by a factor of
10, depending on the number of configured decimal points. Example: Value of 31.78 will be read as 3178.
REGISTERS 31 TO 45 – SIM CARD IDENTIFICATION
Code IMSI inscribed on the SIM card connected to the AirGate-GPRS (in ASCII).
REGISTER 46 – GSM SIGNAL LEVEL
Indicates the current level of GSM signal intensity in dBm.
REGISTER 51 – STATUS 1
Indicates the state of the alarms and errors in the analog/digital input channels.
Bit
Function
0
Alarm state 1 (1 = in alarm)
1
Alarm state 2 (1 = in alarm)
2
Alarm state 3 (1 = in alarm)
3
Alarm state 4 (1 = in alarm)
4
Alarm state 5 (1 = in alarm)
5
Alarm state 6 (1 = in alarm)
6
Alarm state 7 (1 = in alarm)
7
Alarm state 8 (1 = in alarm)
8
Error in input channel 1 (1 = in error)
9
Error in input channel 2 (1 = in error)
REGISTER 52 – STATUS 2
Indicates errors in remote channels, i.e., indicates that the requested slave did not respond to the Modbus command.
Bit
Function
0
Error in remote channel 1 (1 = in error)
1
Error in remote channel 2 (1 = in error)
2
Error in remote channel 3 (1 = in error)
3
Error in remote channel 4 (1 = in error)
4
Error in remote channel 5 (1 = in error)
5
Error in remote channel 6 (1 = in error)
6
Error in remote channel 7 (1 = in error)
7
Error in remote channel 8 (1 = in error)
8
Error in remote channel 9 (1 = in error)
9
Error in remote channel 10 (1 = in error)