Modbus commands and registers table, Supported modbus commands, Read holding registers – 03h – NOVUS AirGate-GPRS User Manual
Page 27: Write single register – 06h, Write multiple registers – 16h, Table of holding registers
AirGate-GPRS
NOVUS AUTOMATION
27/29
MODBUS COMMANDS AND REGISTERS TABLE
The AirGate-GPRS accepts some Modbus commands that are sent to its Modbus’ own address, operating as a network
slave. Commands forwarded to other slaves (routing) will be sent in a transparent way. The following listed Modbus RTU
commands (functions) are implemented, and these are interpreted by AirGate-GPRS. For further information about each
command and the Modbus protocol in general, access the websit
SUPPORTED MODBUS COMMANDS
READ HOLDING REGISTERS – 03H
This command can be used to read a value of one or up to the maximum consecutive holding registers, as shown in the
“Table of Holding Registers”.
WRITE SINGLE REGISTER – 06H
This command can be used to write on a holding register, as shown in the “Table of Holding Registers”.
WRITE MULTIPLE REGISTERS – 16H
This command can be used to write in multiple holding registers, as shown in the “Table of Holding Registers”.
TABLE OF HOLDING REGISTERS
The specified addresses correspond to the low level physical addresses, where zero (0) corresponds to the address PLC
40001. The Minimum and Maximum columns have a range of valid values for each parameter. The R/W column
indicates if the parameter is for reading and writing (R/W) or if it is only reading ® The Mnemonic SuperView states what
the register mnemonic is for in the SuperView software.
Address
Description
Minimum
Maximum
R/W
Mnemonic
SuperView
0
Serial number (word high)
0
65535
R
SerialNumber_H
1
Serial number (word low)
0
65535
R
SerialNumber_L
2
Firmware version
0
999
R
FirmwareVersio
n
3
Value read by the analog/digital channel 1 (whole 16 bits with
signal)
-32768
32767
R
AnDig_Ch1
4
Value read by the analog/digital channel 2 (whole 16 bits with
signal)
-32768
32767
R
AnDig_Ch2
5
Value read by remote channel 1 (whole 16 bits with signal)
-32768
32767
R
Remote_01
6
Value read by remote channel 2 (whole 16 bits with signal)
-32768
32767
R
Remote_02
7
Value read by remote channel 3 (whole 16 bits with signal)
-32768
32767
R
Remote_03
8
Value read by remote channel 4 (whole 16 bits with signal)
-32768
32767
R
Remote_04
9
Value read by remote channel 5 (whole 16 bits with signal)
-32768
32767
R
Remote_05
10
Value read by remote channel 6 (whole 16 bits with signal)
-32768
32767
R
Remote_06
11
Value read by remote channel 7 (whole 16 bits with signal)
-32768
32767
R
Remote_07
12
Value read by remote channel 8 (whole 16 bits with signal)
-32768
32767
R
Remote_08
13
Value read by remote channel 9 (whole 16 bits with signal)
-32768
32767
R
Remote_09
14
Value read by remote channel 10 (whole 16 bits with signal)
-32768
32767
R
Remote_10
15
State of GSM connection (0=disconnected; 1 = connected;
2=connected and authenticated)
0
2
R
GSM_Status
31
SIM Card Identification – characters 1 and 2
-32768
32767
R
-
32
SIM Card Identification – characters 3 and 4
-32768
32767
R
-
33
SIM Card Identification – characters 5 and 6
-32768
32767
R
-
34
SIM Card Identification – characters 7 and 8
-32768
32767
R
-
35
SIM Card Identification – characters 9 and 10
-32768
32767
R
-
36
SIM Card Identification – characters 11 and 12
-32768
32767
R
-
37
SIM Card Identification – characters 13 and 14
-32768
32767
R
-
38
SIM Card Identification – characters 15 and 16
-32768
32767
R
-
39
SIM Card Identification – characters 17 and 18
-32768
32767
R
-
40
SIM Card Identification – characters 19 and 20
-32768
32767
R
-
41
SIM Card Identification – characters 21 and 22
-32768
32767
R
-
42
SIM Card Identification – characters 23 and 24
-32768
32767
R
-
43
SIM Card Identification – characters 25 and 26
-32768
32767
R
-
44
SIM Card Identification – characters 27 and 28
-32768
32767
R
-
45
SIM Card Identification – characters 29 and 30
-32768
32767
R
-