NOVUS RHT-Air User Manual
Page 7
RHT-Air
NOVUS AUTOMATION
7/8
REGISTER 39 – TEMPERATURE VALUE (ºC or ºF)
It contains the value of temperature measurement in an engineering unit,
including the users’ offset corrections for temperature. The decimal point is
fixed in one place, the value has no point and must be provided in the
reading software.
REGISTER 40 – RELATIVE HUMIDITY VALUE (%)
It contains the value of relative humidity measurement in an engineering
unit, including the users’ offset corrections for temperature. The decimal
point is fixed in one space, the value has no point and must be provided in
the reading software.
REGISTER 41 – DEW POINT VALUE (ºC or ºF)
It has the value of the measurement in an engineering unit. The decimal
point is fixed in one place, the value has no point and must be provided in
the reading software.
TABELA DE REGISTRADORES RETENTIVOS
The specified addresses correspond to lower level physical addresses, as zero (0) corresponds to the PLC 40001 address. The columns reserved for minimum and maximum
contain a range of valid values for each parameter. The column reserved for R/W indicates whether the parameters are meant for reading and writing (R/W) or reading only (R).
ADDRESS
DESDRIPTION
MINIMUM
MAXIMUM
R/W
0
Retentive register used to manage the RHT-Air configuration stages. (Used by
DigiConfig)
0
7
R/W
1
Title
-
-
R/W
2
Title
-
-
R/W
3
Title
-
-
R/W
4
Title
-
-
R/W
5
Title
-
-
R/W
6
PANID
0
65535
R/W
7
Encryption
0
1
R/W
8
Security keys 0 and 1
0
65535
R/W
9
Security keys 2 and 3
0
65535
R/W
10
Security keys 4 and 5
0
65535
R/W
11
Security keys 6 and 7
0
65535
R/W
12
Security keys 8 and 9
0
65535
R/W
13
Security keys 10 and 11
0
65535
R/W
14
Security keys 12 and 13
0
65535
R/W
15
Security keys 14 and 15
0
65535
R/W
16
Power Level
0
7
R/W
17
Reserved
-
-
R
18
Serial Number (word high)
0
65535
R
19
Serial Number (word low)
0
65535
R
20
Long MAC address 0 and 1
0
65535
R
21
Long MAC address 2 and 3
0
65535
R
22
Long MAC address 4 and 5
0
65535
R
23
Long MAC address 6 and 7
0
65535
R
24
Short MAC address
0
65535
R
25
Firmware version
0
65535
R
26
Product code
103
103
R
27
Operation channel
11
25
R
28
LQI – Link quality indicator
-100
-15
R
29
Battery power (V)
**
0
3700
R
30
Time of last publication (100 ms)
0
65535
R
31
Modbus Address
1
247
R/W
32
Update time (s)
15
1800
R/W
33
Indication mode
0
3
R/W
34
Measurement unit configuration
0
1
R/W
35
Disables Configuration through a Button
0
1
R/W
36
User Offset For Temperature
*
-100
100
R/W
37
User Offset For Humidity
*
-100
100
R/W
38
Error value
-9999
9999
R/W
39
Temperature value (ºC or ºF)
*
-400
800
R
40
Relative Humidity value (%)
*
0
1000
R
41
Dew Point Value (ºC or ºF)
*
-400
800
R
*
For the abovementioned table ranges, one decimal place should be considered. Example: -100 means -10.0.
**
For the abovementioned table ranges, three decimal places should be considered. Example: 3600 means 3600 V.