I/o cycle (inputs and outputs), Calibration cycle, Spxl – NOVUS Controller N2000 User Manual
Page 8: E.rsp, Rsll, Rsxl, Ieov, Prty, Addr, Io 1
Controller N2000
NOVUS AUTOMATION
8/11
Spxl
Setpoint High
Limit
Defines the upper limit for adjustment of SP.
For the linear analog input types available (0-20 mA,
4-20 mA, 0-50 mV and 0-5 V), defines the maximum
PV indication range, besides limiting the SP
adjustment.
Defines upper limit for range retransmission PV and
SP.
e.rsp
Enable
Remote
SP
Enables remote SP.
YES
-Enables the Function
No
-Does not enable the Function
This parameter is not displayed when the remote SP
selection is defined by a Digital Input.
rsp
Remote
SP
Defines the signal type for the remote SP.
0-20
-current of 0-20 mA
4-20
-current of 4-20 mA
0-5
-voltage of 0-5 V
0-10
-voltage of 0-10 V
Parameter displayed when remote SP is enabled.
Rsll
Remote Set Point Low Limit: Selects the lower range
for indication of the Remote Setpoint.
Rsxl
Remote Set Point High Limit: Selects the upper
range for indication of the Remote Setpoint.
IEov
Percentage output value that will be transfer to MV
when the SAFE output function is enabled. If 1eov =
0, the SAFE output function is disabled and the
outputs are turned off in the occurrence of a sensor
fail.
Bavd
Baud Rate
Serial Communication Baud Rate selection, in kbps:
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 e 115.2
prty
Parity
Parity of the serial communication.
none
-Without parity
Ewem -Even parity
0dd
-Odd parity
Addr
Address
Slave Address Selection: Identifies a slave in the
network. The possible address numbers are from 1 to
247.
I/O CYCLE (INPUTS AND OUTPUTS)
Io 1
I/O 1 Function: Selects the I/O function to be used at
I/O 1 (relay 1).Refer to Table 2 for functions.
Io 2
I/O 2 Function: Selects the I/O function to be used at
I/O 2 (relay 2). Refer to Table 2 for functions.
Io 3
I/O 3 Function: Selects the I/O function to be used at
I/O 3 (relay 3). Refer to Table 2 for functions.
Io 4
I/O 4 Function: Selects the I/O function to be used at
I/O 4 (relay 4). Refer to Table 2 for functions.
Io 5
I/O 5 Function: Selects the I/O function to be used at
I/O 5 (relay 5).Refer to Table 2 for functions.
Io 6
I/O 6 Function: Selects the I/O function to be used at
I/O 6 (relay 6). Refer to Table 2 for functions.
f.fnc
F Key Function: Selects the I/O function assigned to
the front panel
key. Available functions are:
off
-Key not used;
rvn
-Start/Stop the controller (RUN function);
rSP
-Select remote setpoint;
kprg
-Execute/Hold ramp and soak profile;
PR1
-Enable/Disable ramp and soak profile 1;
aven
Enable The
Key – Enable or disable operation of
the
key.
Yes
key enabled.
NO
key disabled.
CALIBRATION CYCLE
All input and output types are factory calibrated. This cycle should
only be accessed by experienced personnel. If in doubt do not press
the or keys in this cycle.
pass
Password
Input of the Access Password.
This parameter is presented before the protected
cycles. See item Protection of Configuration.
(alib
Calibration
Allows instrument calibration.
YES
-Perform calibration
NO
-Do not perform calibration
Inl(
Input Low
Calibration
Input Low Calibration. Enter the value corresponding
to the low scale signal applied to the analog input.
See section MAINTENANCE / Input Calibration.
Inx(
Input High
Calibration
Input High Calibration. Enter the value corresponding
to the full scale signal applied to the analog input.
See section MAINTENANCE / Input Calibration.
rsL(
Remote SP
Low
Calibration
Remote SP Low Calibration. Enter the value
corresponding to the low scale signal applied to the
remote SP input.
See section MAINTENANCE / Input Calibration.
Rsx(
Remote SP
High
Calibration
Remote SP High Calibration. Enter the value
corresponding to the full scale signal applied to the
remote SP input.
See section MAINTENANCE / Input Calibration.
ovL(
Output Low
Calibration
Declaration of lower value present at analog output
See section MAINTENANCE / Input Calibration.
Ovx(
Output High
Calibration
Declaration of upper value present at analog output.
See section MAINTENANCE / Input Calibration.
(j
Cold
Junction
Cold Junction Offset Calibration: Sets the cold
junction offset calibration.
Pas.(
Password
Allows defining a new access password (≠0).
Prot
Protection
Sets up the Protection Level. See Table 6.