beautypg.com

I/o cycle (inputs and outputs), Calibration cycle, Spxl – NOVUS Controller N2000 User Manual

Page 8: E.rsp, Rsll, Rsxl, Ieov, Prty, Addr, Io 1

background image

Controller N2000

NOVUS AUTOMATION

8/11

Spxl

Setpoint High

Limit

Defines the upper limit for adjustment of SP.
For the linear analog input types available (0-20 mA,

4-20 mA, 0-50 mV and 0-5 V), defines the maximum

PV indication range, besides limiting the SP

adjustment.
Defines upper limit for range retransmission PV and

SP.

e.rsp

Enable

Remote

SP

Enables remote SP.

YES

-Enables the Function

No

-Does not enable the Function

This parameter is not displayed when the remote SP

selection is defined by a Digital Input.

rsp

Remote

SP

Defines the signal type for the remote SP.

0-20

-current of 0-20 mA

4-20

-current of 4-20 mA

0-5

-voltage of 0-5 V

0-10

-voltage of 0-10 V

Parameter displayed when remote SP is enabled.

Rsll

Remote Set Point Low Limit: Selects the lower range

for indication of the Remote Setpoint.

Rsxl

Remote Set Point High Limit: Selects the upper

range for indication of the Remote Setpoint.

IEov

Percentage output value that will be transfer to MV

when the SAFE output function is enabled. If 1eov =

0, the SAFE output function is disabled and the

outputs are turned off in the occurrence of a sensor

fail.

Bavd

Baud Rate

Serial Communication Baud Rate selection, in kbps:
1.2, 2.4, 4.8, 9.6, 19.2, 38.4, 57.6 e 115.2

prty

Parity

Parity of the serial communication.

none

-Without parity

Ewem -Even parity

0dd

-Odd parity

Addr

Address

Slave Address Selection: Identifies a slave in the

network. The possible address numbers are from 1 to

247.

I/O CYCLE (INPUTS AND OUTPUTS)

Io 1

I/O 1 Function: Selects the I/O function to be used at

I/O 1 (relay 1).Refer to Table 2 for functions.

Io 2

I/O 2 Function: Selects the I/O function to be used at

I/O 2 (relay 2). Refer to Table 2 for functions.

Io 3

I/O 3 Function: Selects the I/O function to be used at

I/O 3 (relay 3). Refer to Table 2 for functions.

Io 4

I/O 4 Function: Selects the I/O function to be used at

I/O 4 (relay 4). Refer to Table 2 for functions.

Io 5

I/O 5 Function: Selects the I/O function to be used at

I/O 5 (relay 5).Refer to Table 2 for functions.

Io 6

I/O 6 Function: Selects the I/O function to be used at

I/O 6 (relay 6). Refer to Table 2 for functions.

f.fnc

F Key Function: Selects the I/O function assigned to

the front panel

key. Available functions are:

off

-Key not used;

rvn

-Start/Stop the controller (RUN function);

rSP

-Select remote setpoint;

kprg

-Execute/Hold ramp and soak profile;

PR1

-Enable/Disable ramp and soak profile 1;

aven

Enable The

Key – Enable or disable operation of

the

key.

Yes

key enabled.

NO

key disabled.

CALIBRATION CYCLE
All input and output types are factory calibrated. This cycle should

only be accessed by experienced personnel. If in doubt do not press

the or keys in this cycle.

pass

Password

Input of the Access Password.
This parameter is presented before the protected

cycles. See item Protection of Configuration.

(alib

Calibration

Allows instrument calibration.

YES

-Perform calibration

NO

-Do not perform calibration

Inl(

Input Low

Calibration

Input Low Calibration. Enter the value corresponding

to the low scale signal applied to the analog input.
See section MAINTENANCE / Input Calibration.

Inx(

Input High

Calibration

Input High Calibration. Enter the value corresponding

to the full scale signal applied to the analog input.
See section MAINTENANCE / Input Calibration.

rsL(

Remote SP

Low

Calibration

Remote SP Low Calibration. Enter the value

corresponding to the low scale signal applied to the

remote SP input.
See section MAINTENANCE / Input Calibration.

Rsx(

Remote SP

High

Calibration

Remote SP High Calibration. Enter the value

corresponding to the full scale signal applied to the

remote SP input.
See section MAINTENANCE / Input Calibration.

ovL(

Output Low

Calibration

Declaration of lower value present at analog output
See section MAINTENANCE / Input Calibration.

Ovx(

Output High

Calibration

Declaration of upper value present at analog output.
See section MAINTENANCE / Input Calibration.

(j

Cold

Junction

Cold Junction Offset Calibration: Sets the cold

junction offset calibration.

Pas.(

Password

Allows defining a new access password (≠0).

Prot

Protection

Sets up the Protection Level. See Table 6.