beautypg.com

Troubleshooting – COOK HMD EN User Manual

Page 9

background image

9

No

No

No

No

No

Is the proper power

supply at the main

disconnect?

1. Compare the supplied voltage, hertz, and phase with the motor’s

nameplate information.

2. Make sure disconnect switch is on.

Replace 480-120v transformer #A

1. Make sure supply switch is on.

1. Correct supply fan overload if tripped. Check for proper voltage, amps

and RPMs.

2. Check optional exhaust fan interlocks

Is there 120 VAC

between terminals X2 &

X1 on transformer #A?

Is there 120 VAC between

terminal block #2 &

circuit breaker terminal 2?

Is there 120 VAC

between terminal blocks

1 & 5?

Is there 120 VAC

between across A1 &

A2 on supply contactor?

1. Replace fan belt, if broken.

2. Repair or replace motor or capacitor if needed.

3. Repair motor fuse if needed.

4. Repair or replace one or more of the motor

wiring legs, if needed.

At this time the supply contactor

should pull in, passing power to the

supply motor & blower should start.

Yes

Yes

Yes

Yes

Yes

1. Install the optional damper limit switch, if not installed. If holding, wait

for actuator to fully open or adjust the limit switch.

2. Repair or replace fan relay if not energizing. Check for loose

connection.

Blower does not operate

Troubleshooting

Refer to the control panel parts list when troubleshooting.