COOK Curtain Style Ceiling Radiation Damper User Manual

Curtain style ceiling radiation damper, Installation instruction

background image

1

4-3/16

A

B

C

Gemini

Fire Rated

Ceiling Assembly

3-5/8

A x B

#10 x 3/4 speed screws
2 per side minimum
6" max spacing

Grille

1/4" X 20 tpi "all-thread"

or 12 ga steel hanging wire

Hanging Vibration Isolator

(Optional)

Ceiling Radiation Damper

Structural Support

CRD Model # Gemini Fan Model

A

B

C

CRD1

120

14-1/2

12-3/8

6-3/16

CRD1

140

14-1/2

12-3/8

6-3/16

CRD1

160

14-1/2

12-3/8

6-3/16

CRD1

180

14-1/2

12-3/8

6-3/16

CRD2

220, 240

12-5/8

10-1/8

5-1/16

CRD3

320, 340

12-5/8

11-1/8

5-9/16

CRD4

420

17-5/8

12-1/4

6-1/8

CRD4

520

17-5/8

12-1/4

6-1/8

CRD4

620

17-5/8

12-1/4

6-1/8

CRD4

640

17-5/8

12-1/4

6-1/8

CRD4

720

17-5/8

12-1/4

6-1/8

CRD4

740

17-5/8

12-1/4

6-1/8

Loren Cook Company’s curtain style ceiling radiation damper models CRD1, CRD2, CRD3 and CRD4 are classified by UL to

function as heat barriers in air handling penetrations through fire resistive membrane ceiling assemblies. These dampers are
for use in lieu of hinged door type dampers in fire resistive floor-ceiling or roof-ceiling designs which contain air ducts and
specify hinged door type dampers over each duct outlet, as covered in UL’s Fire Resistance Directory. The CRD dampers can be
installed either with a specific size Loren Cook Company Model Gemini fan as a listed fan and damper assembly or as a stand-
alone damper. The following installation instructions show the recommended installation procedures for the CRD’s with the
Gemini fan. If the CRD is installed as a stand-alone damper, then a 16 ga. steel support channel must be attached to the
damper. Use 12 SWG galvanized steel wire or all thread to attach the damper to a supporting structural member. Where it is
necessary to cut a main runner or cross tee, each cut end shall be supported by a vertical No. 12 SWG hanger wire. A 1/2”
(13mm) clearance shall be maintained between the duct outlet and each cut end at main runner and cross tee. The duct outlet
shall be located so that no more than one main runner or cross tee is cut when penetrating the ceiling membrane. Consult with
local authorities that have jurisdiction with regard to local codes and guidelines regarding installation.

Curtain Style Ceiling Radiation Damper

INSTALLATION INSTRUCTION

Meets NFPA 90A requirements.
Meets BOCA, SBCCA, UBC requirements.
The City of New York 460-88-5A
California State Fire Marshall 3225-0935:102

Curtain Style Ceiling Radiation Dampers - January 2002

See details on

UL Classification Marking

on enclosed product.