Campbell Scientific PC400 Datalogger Support Software User Manual
Page 245

Appendix C. Log Files and the LogTool Application
TABLE C-1. Transaction Log Messages
Code
Message Text
Message Parameters
Message Meaning
User Response to
Message
100
Table mount
failed
Table name; Operating
system information
regarding the failure
The server was not
able to create a data
collection area from
the stored table
configuration file or
new table definitions.
This could be the
result of trying to
create table files that
are too large for the
computer system.
Check the computer
operating system
integrity. Verify that
the PC400 system
configuration files exist
and the directory has
not been corrupted.
101 Add
record
failed
Table name; Beginning
record number; End record
number; A reason for the
failure
The server was not
able to write data
records to the data
storage area.
This indicates a
problem writing to files
on the computer hard
disk. Verify write
permissions are set and
that there is sufficient
space left on the disk.
102 Collect
area
skipped
warning
Collect area name
The specified collect
area was skipped
because the
associated table has
not been initialized
by the server yet.
During system startup
this is a normal
message. If it occurs at
other times contact an
application engineer.
103 Collect
area
skipped error
Collect area name
The specified collect
area was skipped
because the server
could not initialize
the associated table.
See message 100
C-11