Campbell Scientific PC400 Datalogger Support Software User Manual
Page 239

Appendix C. Log Files and the LogTool Application
TABLE C-1. Transaction Log Messages
Code
Message Text
Message Parameters
Message Meaning
User Response to
Message
36
Logger table
definitions have
changed
The
server
has
detected a change in
the table definitions
in the datalogger.
A change in table
definitions indicates
that the datalogger
program may have
changed. Before
updating table
definitions make sure
the needed data in the
data cache has been
saved to a file if
desired.
40
Datalogger
message
Severity (S for Status, W
for Warning, F for Fault);
Message text.
This is a message that
has been generated
by the datalogger (or
in some cases the RF
base on behalf of the
datalogger).
Datalogger warning and
fault messages should
be investigated using
the datalogger operators
manual or contacting an
applications engineer at
Campbell Scientific.
41
Records
received
Table name; Beginning
record number; Ending
record number
Datalogger records
have been received
and stored in the data
cache.
42
A datalogger
transaction has
timed out
Time out period in
milliseconds
The server has waited
longer than the
allotted time for the
expected response to
a transaction.
Determine the reason
for the timeout. This is
usually due to a
problem with the
communications path
between the PC and the
datalogger.
43
Terminal
emulation
transaction
started
Terminal
emulation
message has been
sent to the
datalogger.
44
Terminal
emulation
transaction
complete
Terminal
emulation
response message has
been received from
the datalogger.
45
Terminal
emulation
transaction
failed
The
expected
terminal emulation
response from the
datalogger was not
received.
46
Set variable
started
The message to set an
input location, flag or
port has been sent to
the datalogger.
47
Set variable
complete
The
datalogger
has
acknowledged the set
of an input location,
flag or port.
C-5