Specifications / Installation

10

Diagnostics

LED - Normal Functionality

LED

Off

ON

Flash (1Hz)

PWR

No power

applied

10-30Vdc

applied

OK

Self test fail

Self test pass

I/O forcing

enabled.

RUN

Stop mode

Run Mode

Do I/O Mode.

Switch - Normal Functionality

Load switch

1.

Pressing the LOAD switch during power-up boots from the Micro SD card. This starts a Firmware Load if the Micro SD is bootable
and valid firmware files are found on it.

2.

After boot-up, pressing the LOAD switch for 3 seconds either starts a Firmware Load or an Application Load depending upon what
files are found on the Micro SD. If firmware files are found, a Firmware Load is performed. If firmware files are not found and the
DEFAULT.PGM file is found, an Application Load is performed.


Run/Stop switch

1. After boot-up, pressing the RUN/STOP switch for 3 seconds toggles the RCC between RUN and STOP modes.

Switch – Erase Program Function
LOAD and RUN/STOP

1. After boot-up, pressing both Load and RUN/Stop switches for 3 seconds performs an “Erase All” function, which deletes all

application programs.

LED – Diagnostic Functionality

The leds are also used to indicate some fault conditions in the unit. The two leds OK and RUN will flash a number of times depending upon
the fault. There will be a two second gap and the pattern will be repeated. The number of flashes and the associated error are as follows:

No. of flashes

Fault Meaning

2

The MAC ID is empty.

3

The internal MAC file is corrupt.

4

The MAC ID TXT file is invalid.

5

The MAC ID file is not found or the uSD card is empty or missing system files.

Diagnostic Led flashing table.


LED Load Program/Firmware Functionality

LED
OK & RUN

Flashing

Alternately

Flashing

Together

Flashing Stops

Load program
or firmwre

Download in Progress

Download fails,

number of flashes

indicates the error.

Download Complete,

unit reboots (allow 30

seconds).

11. Common Cause of Analog Input Tranzorb Failure
A common cause of Analog Input Tranzorb Failure on Analog Inputs Model 2, 3, 4 & 5: If a 4-20mA circuit is initially wired with loop
power, but without a load, the Analog input could see 24Vdc. This is higher than the rating of the tranzorb. This can be solved by NOT
connecting loop power prior to load connection, or by installing a low-cost PTC in series between the load and Analog input. See
SUP0977-01 for additional details.