Horner APG XL10e OCS Built-in I/O Model 2 I/O User Manual
Page 2
MAN0946-01-EN
Specifications / Installation
1/6/2011
Page 2 of 3
3
Input Wiring Details
J1 Orange
Terminal
Connector
Name
I1
IN1
I2
IN2
I3
IN3
I4
IN4
I5
IN5
I6
IN6
I7
IN7
I8
IN8
H1
HSC1 /IN9
0V
Ground
A1
Analog IN1
A2
Analog IN2
A3
Analog IN3
A4
Analog IN4
0V
Ground
4
Output Wiring Details
J2 Black
Terminal
Connector
Name
C6
Relay 6 COM
R6
Relay 6 NO
C5
Relay 5 COM
R5
Relay 5 NO
C4
Relay 4 COM
R4
Relay 4 NO
C3
Relay 3 COM
R3
Relay 3 NO
C2
Relay 2 COM
R2
Relay 2 NO
C1
Relay 1 COM
R1
Relay 1 NO
H4
HSC4 / IN12
H3
HSC3 / IN11
H2
HSC2 / IN10
5
I/O Register Map
Registers
Description
%I1 to %I24
Digital Inputs
%I32
Output Fault
%I25 to %I31
Reserved
%Q1 to %Q16
Digital outputs
%Q17
Clear HSC1 accumulator to 0
%Q18
Totalizer: Clear HSC2
Quadrature 1-2: Accumulator 1 Reset to max – 1
%Q19
Clear HSC3 Accumulator to 0
%Q20
Totalizer: Clear HSC4
Quadrature 3-4: Accumulator 3 Reset to max – 1
%Q21 to %Q32
Reserved
%AI1 to %AI4
Analog inputs
%AI5, %AI6
HSC1 Accumulator
%AI7, %AI8
HSC2 Accumulator
%AI9, %AI10
HSC3 Accumulator
%AI11, %AI12
HSC4 Accumulator
%AQ1, %AQ2
PWM1 Duty Cycle
%AQ3, %AQ4
PWM2 Duty Cycle
%AQ5, %AQ6
PWM Prescale
%AQ7, %AQ8
PWM Period
%AQ9 to %AQ14
Analog outputs
Registers are allocated
for these I/O points
even though the I/O is
not present for this
model.
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XLe can be wired for Positive Logic inputs or
Negative Logic inputs.
Orange
Digital In /
Analog In
J2 Black
Digital In / Relay Out
Digital Filtering
The chart above demonstrates the effect of digital filtering on an analog
input value. The Digital Filtering level is set in Cscape as part of the I/O
Configuration.
Analog Input Digital Filtering
"WARNING: EXPOSURE TO SOME CHEMICALS MAY DEGRADE
THE SEALING PROPERTIES OF MATERIALS USED IN THE Tyco relay PCJ
Cover / case & base: Mitsubishi engineering Plastics Corp.
5010GN6-30 or 5010GN6-30 M8 (PBT)
Sealing Material: Kishimoto 4616-50K (I part epoxy resin)
It is recommended to periodically inspect the relay for any
degradation of properties and replace if degradation is found