Horner APG XL6 OCS HEXT280C114 User Manual
Page 5
MAN0886-04-EN
Specifications / Installation
__________________________________________________________________________________________________________________________________________________________________
3/2/2010 Page 5 of 6 #1037
Primary Power Port Pins
Pin
Signal
Description
1
Ground
Frame Ground
2
V-
Input Power Supply Ground
3
V+
Input Power Supply Voltage
5
Wiring and Jumpers
•
Wire according to the type of inputs / outputs used and
select the appropriate jumper option.
•
5.1
I/O Jumpers Settings (JP1 – JP3)
5.2
Wiring Examples
J1
Orange
XL103 / XL104
Name
I1
IN1
I2
IN2
I3
IN3
I4
IN4
I5
IN5
I6
IN6
I7
IN7
I8
IN8
H1
HSC1 / IN9
H2
HSC2 / IN10
H3
HSC3 / IN11
H4
HSC4 / IN12
A1
Analog IN1
A2
Analog IN2
0V
Ground
J2 Black
XL103
XL104
0V
Ground
V+
V+ *
NC
No Connect
OUT13
Q12
OUT12
Q11
OUT11
Q10
OUT10
Q9
OUT9
Q8
OUT8
Q7
OUT7
Q6
OUT6
Q5
OUT5
Q4
OUT4
Q3
OUT3
Q2
OUT2 / PWM2
Q1
OUT1 / PWM1
V+* Supply for Sourcing Outputs
J3
Orange
XT104
I13
IN13
I14
IN14
I15
IN15
I16
IN16
I17
IN17
I18
IN18
I19
IN19
I20
IN20
I21
IN21
I22
IN22
I23
IN23
I24
IN24
0V
Ground
Note: The Cscape Module Setup configuration must match the
selected I/O (JP) jumper settings.
I1
0V
001XLE036
12-24VDC
I1
0V
Positive Logic In Negative Logic In
Positive Logic vs. Negative Logic Wiring
The XL6 can be wired for Positive Logic inputs or
Negative Logic inputs.
Location of I/O jumpers (JP)
and wiring connectors
(J1 – J4).
Wiring Specifications
For I/O wiring (discrete), use
the following wire type or
equivalent: Belden 9918, 18
AWG (0.8 mm
2
) or larger.
For shielded Analog I/O wiring,
use the following wire type or
equivalent: Belden 8441, 18
AWG (0.8 mm
2
) or larger.
For CAN wiring, use the
following wire type or equivalent:
Belden 3084, 24 AWG (0.2 mm
2
)
or larger.
Use copper conductors in field
wiring only, 60/75° C
Negative Logic
Positive Logic
JP1 Digital DC Inputs
Default
XL104 J3 Orange
Positive Logic
Digital In
J4
Orange
XL104
Q16
OUT16
Q15
OUT15
Q14
OUT14
XL104 J4 Orange
Positive Logic
Digital Out
Q14
Q15
V+
0V
LOAD
LOAD
10 - 30VDC
Q16
LOAD
J2
J4
Note:
When using JP3 (A1-A2),
e
ach channel can be
independently configured.
Note:
Loop Power requirements
are determined by the
transmitter specification.
20mA
10VDC
JP3
CURRENT OR VOLTAGE INPUTS
001XLE043-R1
A1
A2
A1
A2
1
1
2
2
3
3
4
4
I1
I2
I3
I4
0V
I5
I6
I7
I8
H1
001XLE046
12-24VDC
LOOP
PWR
20mA
0-10VDC
A1
A2
H2
H3
H4
XL103 / 104 J1 Orange
Positive Logic
Digital In
J1
J2
J3
JP3
JP1
001XLE005-R1
J4
Q1
Q2
Q3
Q4
Q9
Q10
Q11
Q12
Q5
Q6
Q7
Q8
V+
0V
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
LOAD
10 - 30VDC
Q13
001XLE024
LOAD
XL103 / 104 J2 Black
Positive Logic
Digital Out
I13
I14
I15
I16
I22
I23
I24
0V
I17
I18
I19
I20
I21
001XLE047
12-24VDC
4.5
Power Port and Wiring