Specifications / Installation

__________________________________________________________________________________________________________________________________________________________________________

3/2/2010 Page 3 of 4 #1037



























4.2

External DIP Switch Settings
























MJ2 Pinouts in Half and Full Duplex Modes






































Table - Ports and Functions

Functions

Port 1 (MJ1)

Port 2 (MJ2)

RS-232

Hardware Handshaking

X

Programming

X

Ladder function
controlled

Serial Downloable
Protocols

RS 485 Full duplex

X

RS 485 Half duplex

4.1

Serial Communications:

MJ1: (RS-232 / RS-485) Use for Cscape programming and
Application-Defined Communications.

MJ2: (RS-232 / RS-485) Use for Application-Defined
Communications.

As seen when looking at the side of the XL6 unit:


The DIP Switches are used for
termination of the RS-485 ports. The
XL6 is shipped un-terminated.


To terminate, select one of the DIP
Switches and configure it based upon
the option that is desired.

Pin

MJ1 Pins

MJ2 Pins

Signal

Direction

Signal

Direction

8

TXD

OUT

TXD

OUT

7

RXD

IN

RXD

IN

6

0 V

Ground

0 V

Ground

5*

+5 60mA

OUT

+5 60mA

OUT

4

RTS

OUT

TX-

OUT

3

CTS

IN

TX+

OUT

2

RX- / TX-

IN / OUT

RX-

IN

1

RX+ / TX+

IN / OUT

RX+

IN

1

8

* +5V 60mA Max

MJ2 Half Duplex Mode

Pin

MJ2 Pins

Signal

Direction

8

TXD

OUT

7

RXD

IN

6

0 V

Ground

5*

+5 60mA

OUT

4

TX-

OUT

3

TX+

OUT

2

TX-/RX-

IN/OUT

1

TX+/RX+

IN/OUT

1

8

Pin

MJ2 Pins

Signal

Direction

8

TXD

OUT

7

RXD

IN

6

0 V

Ground

5*

+5 60mA

OUT

4

TX-

OUT

3

TX+

OUT

2

RX-

IN

1

RX+

IN

1

8

MJ2 Full Duplex Mode

* +5V 60mA Max




SW1 -

ON enables MJ2 RS485 port termination (121 Ohms).

OFF disables MJ2 RS485 port termination.


SW2 & SW3 - ON places MJ2 RS485 port in half-duplex mode.

OFF places MJ2 RS485 port in full-duplex mode.


SW4 -

ON enables MJ1 RS485 port termination (121 Ohms).

OFF disables MJ1 RS485 port termination.

MJ1

MJ2

On

Off

On

Off

On

Off