Horner APG XLe OCS HE-XE102-14 User Manual

Page 2

background image

MAN0855-01-EN

Specifications / Installation

__________________________________________________________________________________________________________________________________________________

7/22/2009 Page 2 of 4 ECN # 956





























5

Wiring and Jumpers


Wire according to the type of inputs / outputs used, and select the
appropriate jumper option.

































5.1.

Wiring Examples

J1 Orange
Terminal
Connector

XE102

Name

I1

IN1

I2

IN2

I3

IN3

I4

IN4

I5

IN5

I6

IN6

I7

IN7

I8

IN8

H1

HSC1 /IN9

0V

Ground

A1

Thermistor 1

A2

Thermistor 2

A3

Thermistor 3

A4

Thermistor 4

0V

Ground




J2 Black
Terminal
Connector

XE102

Name

C6

Relay 6 COM

R6

Relay 6 NO

C5

Relay 5 COM

R5

Relay 5 NO

C4

Relay 4 COM

R4

Relay 4 NO

C3

Relay 3 COM

R3

Relay 3 NO

C2

Relay 2 COM

R2

Relay 2 NO

C1

Relay 1 COM

R1

Relay 1 NO

H4

HSC4 / IN12

H3

HSC3 / IN11

H2

HSC2 / IN10








5.2

I/O Jumpers Settings (JP1)


















5.3

External DIP Switch Settings (or Jumpers Settings)


























6

Derating








J1

JP2

JP1

J2

001XLE025

Location of I/O jumpers (JP)

and wiring connectors

(J1 and J2).

I1

0V

001XLE036

12-24VDC

I1

0V

Positive Logic In Negative Logic In

Positive Logic vs. Negative Logic Wiring

The XLe can be wired for Positive Logic inputs or

Negative Logic inputs.

Wiring Specifications

For I/O wiring (discrete), use the

following wire type or equivalent:

Belden 9918, 18 AWG (0.8 mm

2

)

or larger.

For shielded Analog I/O wiring,

use the following wire type or

equivalent: Belden 8441, 18

AWG (0.8 mm

2

) or larger.

For CAN wiring, use the

following wire type or equivalent:

Belden 3084, 24 AWG (0.2 mm

2

)

or larger.

Use copper conductors in field

wiring only, 60/75° C

Pin

MJ1 Pins

MJ2 Pins

Signal

Direction

Signal

Direction

8

TXD

OUT

TXD

OUT

7

RXD

IN

RXD

IN

6

0 V

Ground

0 V

Ground

5*

+5

60mA

OUT

+5

60mA

OUT

4

RTS

OUT

TX-

OUT

3

CTS

IN

TX+

OUT

2

RX- /

TX-

IN / OUT

RX-

IN

1

RX+ /

TX+

IN / OUT

RX+

IN

1

8

4

Serial Communications:

MJ1: (RS-232 / RS-485) Use for Cscape programming and
Application-Defined Communications.

MJ2:
(RS-232 / RS-485) Use for Application-Defined
Communications.

* +5 on XLe Rev E and later

Note: The Cscape Module Setup configuration must match the

selected I/O (JP) jumper settings.

001XLE026

JP1 Digital DC In / HSC

Positive Negative

Logic Logic

Default

001XLE015

0V ON J1

12-24VDC

R2

C2

R3

C3

R6

C6

R4

C4

R5

C5

R1

C1

H4

H2

H3

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

XE102 J2 Black

Positive Logic

Digital In / Relay Out

Some XLes have jumpers to set
RS-485 port termination, though
most use DIP Switches.

The External Jumpers or DIP
Switches are used for termination
of the RS-485 ports. The XLE is
shipped un-terminated.

To terminate, select one of the
jumpers shipped with the product
and insert it based upon the option
that is desired or, select the switch
and configure based upon the
option that is desired.

Factory Use

(default – none)

MJ2 Termination

(default – none)

MJ1 Termination

(default – none)

001XLE037

As seen when looking at the top of the XLE unit: Refer to
Section 4 for the location of the External Jumpers.

XLE102 Relay Life Expectancy

0

10

20

30

40

1

2

3

4

Contact Current (A)

O

p

e

ra

ti

o

n

(x

1

0

4

)

001XLE037-R1

Factory Use

(default – none)

MJ2 Termination

(default – none)

MJ1 Termination

(default – none)

I1

I2

I3

I4

0V

A1

A2

0V

I5

I6

I7

I8

A3

A4

H1

001XLE067

12-24VDC

T

T

T

T

XE102 J1 Orange

Positive Logic In

Digital In /

Analog In