Appendix “b” - scaling for rate indication 66 – Red Lion LEGEND User Manual
Page 70
![background image](/manuals/408881/70/background.png)
EXAMPLE #2:
The shaft of a positive displacement pump has a 14 tooth sprocket that is
being sensed by a magnetic pickup. It is known that the unit pumps 810 liters
of water per minute, when the shaft is turning 400 RPM. It is desired to have a
display readout in liters per minute.
With the Legend Plus, it is not necessary to deal with time unit conversions.
From the information given, we know that when the shaft has turned 400
revolutions, 810 liters of water will have been pumped. The first step we need
to take is to calculate the number of pulses that occur when 810 liters have
been pumped.
Number of Pulses = # of Rev x Pulses per Rev
= 400 Rev x 14 PPR = 5600 pulses.
We now have all the information necessary to scale the rate. The Total
Scaling, “K
T
”, is calculated using Formula #1 as shown below.
K
T
= Display Units ÷ Number of Pulses = 810 ÷ 5600 = 0.144643
It is noticed that there are more significant digits in the Total Scaling, “K
T
”,
than there are available for the Scale Factor, “SF”. To acquire the maximum
amount of significant digits for the Scale Factor, Formula #2 is used and a
Scale Multiplier value of 0.1 is selected.
SF = K
T
÷ SCM = 0.144643 ÷ 0.1 = 1.4464
The Scale Factor, “SF”, equals 1.4464 (1.44643 rounded to 4 decimal
places). This provides the maximum amount of conversion accuracy possible.
The final step is to select a Rate Conversion Factor. The Rate Conversion
Factor is chosen to be Rate Per Minute as was required.
-68-